Remington QFP40 Manuel D’Utilisation

Page de 68
REMINGTON QFP40 Direct Vent FIREPLACE
Page 28
250-4721   JUNE 2001
VENTING
VENTING INSTALLATION OPTIONS & GUIDELINES
There are four types of direct vent system installations approved for use with the REMINGTON
QFP40. It is very important to maintain a balance between the combustion air intake and the flue
gas exhaust venting system. The types of installation are:
Horizontal Termination (Figure 1)
Vertical Termination (Figure 2)
Into a Class A Metal Chimney (Figure 3)*
Into a Masonry Chimney (Figure 4)*
*USA installations only
Note: Certain limitations as to vent and vertical termination configuration apply, and
must be strictly adhered to. Read this manual carefully.
When planning your installation, it will be necessary to select the proper length of vent pipe for
your particular requirements. The vent graph on page 32 will show the relationship between vertical
and horizontal side wall venting, and will help you to determine the various vent lengths permitted.
It is also important to note the wall thickness. Select the amount of vertical rise desired for “vertical-
to-horizontal”  type  installations.  To  determine  the  length  of  your  pipe  required  for  vertical
installations,  measure  the  distance  from  the  application  flue  outlet  to  the  ceiling,  the  ceiling
thickness, the vertical rise in an attic or second story, and allow for sufficient vent height above the
roofline.  For  two-story  applications,  fire  stops  are  required  at  each  floor  level.  If  an  offset  is
needed in the attic, additional pipe and elbows will be required.
When installing this appliance into an existing masonry chimney, it is important to carefully measure
the  length  of  flex  needed  to  reach  from  the  appliance  outlet  to  the  termination  cap.  If  the  flex
length is too short, a flex coupler will be needed to attach an additional length of flex liner to make
up the difference. If the flex length is too long, the liner could sag below the appliance outlet,
which could result in a potential fire hazard.
10'
       2'
Minimum
3'
Minimum
A masonry chimney or a factory-built chimney must be the required height above the roof
and any other nearby obstructions.  The chimney must be at least three feet higher than
the highest point where it passes through the roof and at least two feet higher than the
highest  part  of  the  roof  or  structure  that  is  within  ten  feet  of  the  chimney,  measured
horizontally.    See  2-10-3  diagram  below.    These  are  safety  requirements  and  are  not
meant to assure proper flue draft.
2-10-3 VERTICAL TERMINATION RULE