Remington QFP40 Manuel D’Utilisation

Page de 68
REMINGTON QFP40 Direct Vent FIREPLACE
Page 38
250-4721   JUNE 2001
VERTICAL INSTALLATION INSTRUCTIONS
USING GS SERIES PIPE
Step 1. Check the installation instructions for required 1" clearances (air space) to com-
bustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, or
other  nearby  combustible  surfaces.    See  page  40,    Fig.  16.    Do  not  pack  air
space with insulation. Check the instructions below for maximum vertical rise of
the  venting  system,  and  any  maximum  horizontal  offset  limitations. All  offsets
must fall within the set parameters of the vent graph located on page 31.
NOTE: Maximum vertical rise allowable is 30' (900mm) (Figure 10).
30' MAX
NOTE:      Maximum  number  of  45°  elbows  permitted  for  a  vertical  installation  is  eight,
provided their installation does not decrease maximum vertical rise (as specifiedby
Vent graph, on page 31).
NOTE:  Maximum number of 90° elbows permitted for a vertical installation is four, pro-
vided the termination falls within the shaded area shown in vent graph on page
32.  See also Figure         12 below.  ADDITIONAL RESTRICTION:  This installa-
tion may not have two horizontal sections connected by 90° elbows.
Step 2. Set the gas stove in its desired location. Drop a plumb bob down from the ceiling
to the position of the stove flue exit, and mark the location where the vent will
penetrate the ceiling. Drill a small hole at this point. Next, drop a plumb bob from
the roof to the hole previously drilled in the ceiling, and mark the spot where the
vent will penetrate the roof. Determine if ceiling joists, roof rafters, or other fram-
ing  will  obstruct  the  venting  system. You  may  wish  to  relocate  the  stove,  or  to
offset, as shown in Figure 11, to avoid cutting loadbearing members.
1'
2'
1'
2'
1'
VENTING
FIG. 10
FIG. 11
FIG. 12