Empire Comfort Systems 3)(N Manuel D’Utilisation

Page de 60
23552-4-0408
Page 18
To Use the Vent Graph (Figure 20)
1.  Determine the height of the center of the horizontal vent 
pipe. Using this dimension on the Sidewall Vent Graph, 
locate  the  point  it  intersects  with  the  slanted  graph 
line.
2.  From the point of this intersection, draw a vertical line 
to the bottom of the graph.
3.  Select the indicated dimension, and position the unit in 
accordance with same.
EXAMPLE A:
If the vertical dimension from the floor of the unit is 35 
feet, the horizontal run to the outer wall flange must not 
exceed 6.5 feet.
EXAMPLE B:
If the vertical dimension from the floor of the unit is 6.5 
feet, the horizontal run to the outer wall flange must not 
exceed 14.5 feet.
SPECIAL NOTE: For each 45 degree elbow installed in 
the horizontal run, the length of the horizontal run MUST 
be reduced by 18" (457 mm). This does not apply if the 45 
degree elbows are installed on the vertical part of the vent 
system. Reduce 3' for every 90° elbow.
Example: According to the chart the maximum horizontal 
vent length is 20' and if two 45 degree elbows are required 
in the horizontal vent it must be reduced to 17'.
The maximum number of 45 degree elbows permitted per 
side wall installation is two (2). These elbows can be installed 
in either the vertical or horizontal run.
Note:  On  vertical  venting  the  first  elbow  does  not  get 
counted.
  Acceptable vertical and horizontal vent run.
 
(40' maximum vertical and 20' maximum horizontal)
  Unacceptable vertical and horizontal vent run.
Figure 20
Venting Graph (Dimensions in Feet)
VERTICAL
DIMENSION
FROM
THE
BOTTOM
OF
THE
UNIT
TO
THE
CENTER
OF
THE
FLUE
OUTLET
WITH
VERTICAL
OR
HORIZONTAL
TERMINATION
CAPS
VENTING FIREPLACE - TOP