TROUBLESHOOTING
 WARNING: Turn off heater and let cool before servicing. Only a 
qualified service person should service and repair heater.
 WARNING: Turn off heater and let cool before servicing. Only a 
qualified service person should service and repair heater.
OBSERVED PROBLEM
Pilot will not stay lit
Pilot lit but no flame on burner
Frequent pilot outage
POSSIBLE CAUSE
1. Defective thermocouple
1. Remote or wires defective
2. Thermopile  not  generating 
sufficient milivoltage
3. Plugged burner orifice
1. Pilot flame may be too low 
or  blowing  (high)  causing 
safety pilot to “drop out”
REMEDY
1. Check  pilot  flame.  It  must 
impinge on thermocouple
2. Clean or adjust pilot for maxi-
mum flame impingement on 
thermocouple
3. Ensure  the  connection  be-
tween valve and thermocouple 
are tight and secure
4. Check  thermocouple  with 
millivolt meter. Take reading 
at thermocouple terminals of 
gas valve with remote control 
off. It should read 18 millivolts 
minimum. Replace faulty ther-
mocouple if reading is below 
specified minimum
1. Check remote wires for proper 
connections.  Place  jumper 
wire  across  terminals  at  re-
mote control. If burner comes 
on,  replace  remote.  If  okay, 
place  jumper  wire  across 
remote  control  at  valve.  If 
burner  comes  on,  wires  are 
faulty or connections are bad
2. Check  thermopile  with  mil-
livolt meter. Take reading at 
thermopile  terminals  of  gas 
valve with remote control off. 
It should read 325 millivolts 
minimum. Replace thermopile 
if reading is below specified 
minimum
3. Check burner orifice for stop-
page and remove
1. Clean and/or adjust pilot flame 
for maximum flame impinge-
ment on thermocouple