Hampton Direct U32 Manuel D’Utilisation

Page de 40
8
U32-5 FPI Direct Vent Gas Insert
VENTING
THE APPLIANCE MUST NOT BE 
CONNECTED TO A
CHIMNEY FLUE SERVING A 
SEPARATE SOLID FUEL
BURNING APPLIANCE.
This appliance is designed to be attached to 
two 3" (76mm) co-linear aluminium fl ex running 
the full length of the chimney. The fl ue length 
must be a minimum length of 8 '  (2.44m) and 
a maximum of 35' (10.7m). See chart below for 
minimum distances from roof. Periodically check 
that the vent is unrestricted.
Masonry chimneys may take various contours 
which the fl exible liner will accommodate. 
However, keep the fl exible liner as straight as 
possible
, avoid unnecessary bending.
The Air Intake pipe must  be attached to the inlet 
air collar of the termination cap.
Part # 
Description
948-305 
3" Flex - 35 ft.
946-529 Co-linear 
DV 
Vertical 
 Termination 
Cap
GAS CONNECTION 
GAS CONNECTION WARNING:
Only persons licensed to work 
with gas piping may make the 
necessary gas connections 
to this appliance.  
1)  If the appliance is to be installed into an 
existing chimney system, thoroughly clean 
the masonry or factory built fi replace.
2)  The appliance is provided with an opening on 
the left hand side of the control compartment. 
A 3/8" NPT gas supply pipe must be brought 
near this inlet hole. 
3)  Locate the center point where the vent 
will pass through the chimney above the 
appliance.  Move the appliance into the 
exact location where it is to be installed.  
Ensure that the Insert is level.
Diagram 3
INSTALLATION
Note:  A noncombustible mantel may be 
installed at a lower height if the 
framing is made of metal studs 
covered with a noncombustible 
board.
FLUE LINER 
INSTALLATION
1)  Cut the fl ex liner as required.
 
2)  Mark the end of one liner to indicate 
Inlet.
3)  Connect the other end of the above liner to 
the inlet side of the termination adaptor, seal 
connection with high temperature silicone. 
Secure with gear clamp.
4)  Connect the 2nd liner to the exhaust side 
of the adaptor, seal connection with high 
temperature silicone. Secure with gear 
clamp.
Alternate Approved Caps
980 Vertical 
Termination 
Cap
991 High 
Wind 
Cap
923GK 3" 
Co-linear 
Adaptor 
with 
fl 
ashing
In areas of consistently high winds, we 
recommend using the Simpson Dura-Vent 
System (923GK adapter and 991 high-wind 
cap).
5) Install 
fl 
ashing.
6)  Insert both liners into chimney, passing 
through the damper opening.
7) Install 
termination 
cap.
8) Connect the marked end of the liner to 
the inlet  collar of the vent connector plate 
marked with an "I", seal connection with 
high temperature silicone. Secure with gear 
clamp.
The Air Intake pipe must  be attached to the 
inlet air collar of the termination cap.