Johnson Controls BQ 060 Manuel D’Utilisation

Page de 40
364985-XIM-B-0508
Johnson Controls Unitary Products
11
ECONOMIZER/MOTORIZED DAMPER AND RAIN HOOD
The instruction for the optional economizer/motorized
damper and rain hood can be found in form 035-
07364-000. Use these instructions when field assem-
bling an economizer rain hood onto a unit. The outdoor
and return air dampers, the damper actuator, the
damper linkage, the outdoor and return air divider baf-
fles, and all the control sensors are factory mounted as
part of the “Factory installed” economizer/motorized
damper options.
POWER EXHAUST/BAROMETRIC RELIEF DAMPER AND 
RAIN HOOD 
The instructions for the power exhaust/barometric relief
damper and rain hood can be found in form 530.18-
N1.10V.
All of the components, including the dampers, hard-
ware, and mounting instructions are shipped in a single
package external from the unit and must be field
assembled and installed.
Power exhaust is only available as a field installed
accessory.
ECONOMIZER AND POWER EXHAUST DAMPER 
SET POINT ADJUSTMENTS AND INFORMATION
Remove the economizer access panel from the unit.
Loosen but do not remove the two panel latches.
Locate the economizer control module, where the fol-
lowing adjustments will be made.
Check that the damper blades move smoothly without
binding; carefully turn the Minimum Position Adjusting
screw (found on the damper control module) fully
clockwise and then set the thermostat indoor fan switch
to the on position and then off, or energize and de-
energize terminals “R” to “G”.
TABLE 3: ELECTRIC HEATER CFM LIMITATIONS
UNIT MODEL SIZE
NOMINAL TONS
VOLTAGE
MINIMUM SUPPLY AIR CFM
HEATER SIZE NOMINAL KW
5
7
10
15
20
30
036
(3)
208/230-1-60
900
900
900
900
900
-
208/230-3-60
900
900
900
900
900
-
460-3-60
-
900
900
900
900
-
600-3-60
-
-
900
900
900
-
048
(4)
208/230-1-60
1200
1200
1200
1200
1200
-
208/230-3-60
1200
1200
1200
1200
1200
-
460-3-60
-
1200
1200
1200
1200
-
600-3-60
-
-
1200
1200
1200
-
060
(5)
208/230-1-60
1500
1500
1500
1500
1500
1500
208/230-3-60
1500
1500
1500
1500
1500
1500
460-3-60
-
1500
1500
1500
1500
1500
600-3-60
-
-
1500
1500
1500
1500
Extreme care must be exercised in turning all
setpoint, maximum, and minimum damper
positioning adjustment screws to prevent twist-
ing them off.