Johnson Controls R-410A Manuel D’Utilisation

Page de 100
505430-BTG-A-0309                                                                                                                                                                                                                                           
6
Johnson Controls Unitary Products
Guide Specifications
Split System Cooling Only Condensing Units
Models: YH-07 thru -20, YJ-10 thru -20 & Split 
System Heat Pump Models: PH-07 thru -20, PJ-15 
thru -20
General
• Factory assembled, single piece, air cooled condensing 
unit designed for outdoor installation.
• Factory wired, piped, and tested for leakage and 
functionality to assure trouble-free installation and start-
up.
• Rated in accordance with ARI Standard 340/360.
• Manufactured in a facility registered under the ISO 9002 
manufacturing quality standard.
• Designed and tested in accordance with ASHRAE 15 
Safety Code for Mechanical Refrigeration and comply 
with NEC.
• Cooling performance rated in accordance with DOE 
and ARI test procedures.
• CSA listed and classified to UL 1995/CAN/CSA No. 
236- M90 standards.
• One year limited parts warranty on complete unit with 
an additional four year compressor warranty.
Unit Operating Characteristics
Operating Range shall be between 125° F to 40° F in cooling 
as standard from factory.
• The capacity of the condensing unit shall meet or 
exceed _____ Btuh at a suction temperature of _____ 
F. The power consumption at full load shall not exceed 
_____ kW.
• The combination of the condensing unit and the 
evaporator or fan coil unit shall have a total net cooling 
capacity of _____ Btuh or greater at conditions of 
_____ cfm entering-air temperature at the evaporator at 
_____ F wet bulb and _____ F dry bulb, and air 
entering the condensing unit at _____F.
• The system shall have an EER of _____ Btuh/ Watt or 
greater at standard ARI conditions.
Installer Shall
• Furnish Brand air-cooled condensing units, heat pump 
or equivalent in accordance with the performance 
schedule shown on the plans, and
• Unit shall be stored and handled in accordance with unit 
manufacturer's instructions.
• Install each unit as shown on the plans in accordance 
with the manufacturer’s recommendations and all 
applicable national and local codes
Unit Construction
• Constructed of zinc-coated, galvanized steel.
• Exterior surfaces bonded and coated with baked 
enamel finish by a powder paint process capable of 
withstanding a minimum of 1000 salt spray hours 
according to ASTM B117.
• Cabinet screws that comply with ASTM B117 salt spray 
test for a minimum of 750 hours.
• Permanently attached heavy-gage perimeter base rails 
with forklift slots and lifting holes.
• Removable access panels to all internal components.
• Separate access panel to controls.
• Access panels to allow outdoor coil cleaning.
Compressor(s)
• Hermetic scroll type, internally protected with high-
pressure relief and over temperature protection.
• Two stage units operate in 50% capacity increments.
• Suction gas cooled
• Voltage range of ±10% of unit nameplate voltage.
• Neoprene isolators minimize sound transmission and 
vibration.
• Belly-band crankcase heaters keep refrigerant from 
diluting sump oil.
• Full charge of compressor oil
Outdoor Condenser Unit Coils
• Draw thru configuration
• Constructed with Micro-channel aluminum fins and 
aluminum tubing. All refrigerant tubing must share a 
common header.
Heat Pump Unit Outdoor Unit Coils
• Draw thru configuration
• Constructed with aluminum plate fins mechanically 
bonded to seamless internally enhanced copper tubes 
with all joints brazed.
Condenser Fans
• Direct driven propeller-type fans
• Statically and dynamically balanced
• Aluminum blades riveted to corrosion resistant steel 
spider brackets.
• Arranged for vertical air discharge.
• Equipped with PVC coated steel wire safety guards.
Condenser Motors
• Totally enclosed, air over cooled.
• Inherent overload protection.
• Permanently lubricated bearings.