LARGE CURB
SMALL CURB
ROOF CURB DETAIL
Wood nailer*
Roofcurb*
Insulation
(field supplied)
*Provided with roofcurb
Cant strip
field supplied
Roofing material
field supplied
Flashing field
supplied
HVAC unit
base rails
Roofcurb
Sealing
Gasket 
HVAC unit
basepan
Anchor screw
A09090
A09415
A09418
C
B
A
F
D
E
G
H
C
B
A
D
E
H
F
G
A09419
UNIT SIZE
CATALOG
NUMBER
A
IN. (mm)
B
IN. (mm)*
C
IN. (mm)
D
IN. (mm)
E
IN. (mm)
F
IN. (mm)
G
IN. (mm)
H
IN. (mm)
Small
CPRFCURB010A00
11 (279)
10 (254)
16 (406)
47.8
(1214)
32.4 (822)
2.7 (69)
30.6 (778)
46.1 (1170)
CPRFCURB011A00
14 (356)
Large
CPRFCURB012A00
11 (279)
14 (356)
43.9
(1116)
42.2 (1072)
CPRFCURB013A00
14 (356)
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16--gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.
IMPORTANT: Do not install large base pan HYBRID HEAT units onto
the small base pan (common curb). The center of gravity on a large base
pan HYBRID HEAT unit could overhang the curb causing an unsafe
condition. Before installing any large base pan unit onto the common
curb, check the “Y” distance in the product literature dimensional drawing
to ensure that “Y” is greater than 14 in. (356 mm). Do not install any large
base pan unit onto the common curb with a “Y” dimension (center of
gravity) less than 14 in. (356 mm).
Fig. 4 -- Roof Curb Dimensions