EMI S1C Manuel D’Utilisation

Page de 40
www.enviromaster.com
3
WLCA/WLHA High Wall Evaporator
ControLs And ComponEnts
Continued
prodUCt dEsCription
The AmericaSeries  WLCA/WLHA  is 
available as a (Dx) direct expansion straight 
cool and heat pump. It offers a contempo-
rary design in a ductless type evaporator and 
combines attractive appearance with high 
efficiency conditioning for small to medium 
size commercial or residential spaces. The 
WLCA/WLHA is equipped with unit mounted 
infrared compatible controls which also sup-
ports 24V remote wall thermostat operation. 
Optional hand held remote is available.
Heat  Pump  models  provide  up  to 
23,000 Btuh of cooling and 20,600 Btuh of 
heating. Electric heat options are available 
for up to 5 kW of supplemental heat.
This American-made evaporator offers 
ease of installation, operation, and service. 
It can be matched with EMI’s S1CA/S1HA 
09-24 and S1CA 30-36 Btuh Single-Zone 
Condensing Units, the S2CA side discharge 
Dual-Zone Condensing Unit, or the T2CA, 
T3CA, and T4CA top discharge Multi-Zone 
Condensing Units.
All  EMI Air  Handlers  are  backed  by 
Enviromaster  International  LLC  and  are 
tested and rated in accordance with ARI 
standards 210/240 and UL 1995.
• Operation modes include Heat, Cool, 
Dry, Fan and Auto Change-over.
• Fan Operation – Auto/On. High or Low 
speed fan 
•  Fan  Purge  –  Fan  remains  on  for 
60  seconds  after  Heat/Cool  call  is 
dropped for improved efficiency (Auto 
mode only) 
• Room air sampling: Selectable time 
intervals  ensure  the  fan  will  cycle 
on  periodically,  in Auto  Fan  Mode 
to  help  eliminate  room  temperature 
stratification. 
• Selectable Fahrenheit (°F) or Cesius 
(°C)
 temperature scale.
•  Dry  mode  –  Operates  cooling  and 
electric heat simultaneously to remove 
humidity. Optional electric heat must 
be selected. 
• Anti-Short Cycle Compressor Pro-
tection.
•  Minimum  on  time  for  heating  and 
cooling 
Helps eliminate room temper-
ature drop and system short cycling.
• Freeze Protection – Prevents evapo-
rator freeze up
.
• Test operation – Allows ease of test-
ing  after  installation  (all  timers  are 
eliminated). 
•  Non-volatile  back-up  memory  will 
maintain control settings  for an indefinite 
period  during  a  power  outage.  When 
power  is  restored  the  equipment  will 
resume operation after a three-minute 
compressor time delay.
• 7-day programmable with copy feature.
• Filter change indicator: A timer fea-
ture indicates when the filter should be 
changed according to the selected time.
• Motorized supply louver with optional 
sweep or six stationary settings.
• Infra red compatible control allows 
use of optional IR hand held controller.
note: 
Unit  mounted  controls  are 
fully functional without the handheld 
remote.
ControLs And ComponEnts
Note: If the control is configured for 
unit mount control do NOT connect 
a wall thermostat to the unit.
• Large LCD Backlit Display
• Single unit mounted control pack-
age
, configurable to either unit mount 
or remote wall thermostat operation, 
reducing  model  number  or  SKU’s 
required.
•  Universal  control  can  be  used  in 
cooling only, cooling with electric heat, 
heat pump, or heat pump with second 
stage electric heat applications.
•  Operational  range  set  point  tem-
perature adjustable between 55°F and 
90°F in one-degree increments.