Ducane (HVAC) L Manuel D’Utilisation

Page de 6
4hp13   Split System heat pump
seer
13
4hp13   Split System heat pump
seer
13
Model Number Guide
4
HP 13
B
24
   P    -    1
A
4 = R410a Refrigerant
Minor Revision Code
HP = Heat Pump
Major Revision Code
13 - 13 SEER Nominal
Electric
p - 208-230V/60Hz/1Ph
B = Wire Guard
L =  Louvered
Nominal Capacity
24 - 24,000 Btuh
Model
Volts/Hz/Phase Voltage 
Range
Min. 
Circuit 
Amp.
Max. 
Over-
current 
Device 
(amps)
Compressor
Fan Motor
Refrig. 
Charge 
(oz.)
Weight (lbs.)
Rated 
Load 
(amps)
Locked 
Rotor 
(amps)
Rated 
Load 
(amps)
Rated HP Nom. 
RPM
Wire Guard/ 
Louvered
4HP13*18P 208-230/60/1 197/253 11.90
20
9.0
48
0.7
1/10
1075
117
151/166
4HP13*24P 208-230/60/1 197/253 11.10
15
8.3
43
0.7
1/10
1075
130
169/185
4HP13*30P 208-230/60/1 197/253
14.4
20
10.6
54
1.1
1/5
1075
159
186/203
4HP13*36P 208-230/60/1 197/253
19.6
30
14.7
74
1.2
1/4
1075
151
197/208
4HP13*42P 208-230/60/1 197/253
20.2
30
15.2
84
1.2
1/4
1075
170
218/229
4HP13*48P 208-230/60/1 197/253
25.1
35
19.1
102
1.2
1/4
1075
267
260/277
4HP13*60P 208-230/60/1 197/253
26.7
40
20.4
105
1.2
1/4
1075
251
262/279
physical and Electrical Data
Unit Dimensions & Sound Ratings
Model
Dimensions
Sound 
Ratings 
(dBa)
A
 (in.)
(in.)
(in.)
4HP13*18P
30
30
34
77
4HP13*24P
30
30
34
78
4HP13*30P
30
30
38
78
4HP13*36P
30
30
26
77
4HP13*42P
30
30
26
77
4HP13*48P
30
30
38
79
4HP13*60P
30
30
42
79
* -B or L
* -B or L