3-3. OPERATIONAL FREQUENCY RANGE
b) Correct the LEV separately by temperature difference “
∆RT” between main/sub indoor coil thermistor.
∆RT
LEV opening
correction (pulse)
10.8
∆RT
2
7.2
∆RT < 10.8
1
∆RT < 7.2
1
In addition, decrease the target discharge temperature corresponding
∆RT.
∆ RT
Temperature to be
decreased (°F)
10.8
∆RT
18
7.2
∆RT< 10.8
9
∆RT < 7.2
9
MXZ-2A20NA
Number of operating
unit
Capacity code
COOL (Hz)
DRY (Hz)
HEAT (Hz)
Min. Max.
Min. Max.
Defrost
1
4
20
65
25
48
92
92
7
20
85
30
48
92
92
9,10 20
100
75
48
100
100
12
20
100
75
48
100
100
2
8 ~ 10
30
105
52
58
112
100
11 ~ 13
30
105
52
58
112
100
14 ~ 16
30
105
52
58
112
100
17 ~
20
105
100
58
112
100
MXZ-3A30NA
Number of operating
unit
Capacity code
COOL (Hz)
DRY (Hz)
HEAT (Hz)
Min. Max.
Min. Max.
Defrost
1
4
15
58
20
22
48
48
7
15
58
25
22
48
48
9,10 15
62
44
22
62
58
12
15
68
44
22
90
58
2
8 ~ 10
24
80
31
35
70
58
11 ~ 13
24
80
31
35
90
58
14 ~ 16
24
80
31
35
94
58
17 ~
24
80
59
35
94
58
3
12 ~
52
90
65
39
94
58
MXZ-2A20NA-
1
Number of operating
unit
Capacity code
COOL (Hz)
DRY (Hz)
HEAT (Hz)
Min. Max.
Min. Max.
Defrost
1
4
20
65
35
48
92
92
7
20
85
34
48
92
92
9,10 20
93
75
48
92
92
12
20
93
75
48
92
92
2
8 ~ 10
30
93
52
58
110
101
11 ~ 13
30
93
52
58
110
101
14 ~ 16
30
93
52
58
110
101
17 ~
30
93
93
58
110
101