Failure to exceed 105ºF (41ºC) within 7 minutes may
result in the premature failure of the hot surface ignit-
er, remote flame sensor, burners and heat exchanger.
It  can  cause  operational  problems,  bad  combustion,
sooting,  flue  gas  spillage  and  reduced  service  life  of
the vent system. The bypass allows part of the heater
discharge  water  to  be  mixed  with  the  cooler  heater
return  water  to  increase  the  heater  inlet  temperature
above  105ºF  (41ºC).  This  precautionary  measure
should prevent the products of combustion from con-
densing in most installations. Warranty claims will be
denied when condensation occurs.
Cold  water  operation  issues  are  applicable  to  both
cold water start and cold water run applications. Cold
water  operation  for  7  minutes  or  less  on  start-up  is
acceptable.  Where  cold  water  starts  will  last  longer
than 7 minutes or where cold water operation is con-
tinuous,  provisions  must  be  made  to  mix  higher
temperature  outlet  water  with  the  colder  inlet  water
and  thereby  raise  the  inlet  temperature  to  at  least
105ºF (41ºC) within the 7-minute time limit.
Cold Water Starts
Frequent (more than once a week) cold water starts,
wherein  the  inlet  water  temperature  remains  below
105ºF (41ºC) for more than 7 minutes, must have cold
water start protection. Known protection methods con-
sist of mixing heated outlet water with the inlet water
with a bypass to raise the inlet to 105ºF (41ºC) or high-
er. Once the system is heated up and has return water
temperatures of 105ºF (41ºC) or higher, the mixing of
outlet water with inlet water is no longer needed and
the bypass can be shut off. If the bypass is not shut off
as  the  system  heats  up,  the  outlet  temperature  may
continue  to  climb  and  actuate  the  high  limit,  thereby
shutting  down  the  heater.  Thus  an  automatic  valve
system,  such  as  a  three-way  proportional  valve  or  a
modulating  two-way  valve  to  control  the  bypass,
should be utilized. 
Cold Water Run
Cold water run differs from cold water start in that the
system water entering the heater remains below 105ºF
(41ºC) continuously. Typically, this is the case in swim-
ming  pool  heating  and  water  source  heat  pump
applications  as  well  as  some  others.  If  the  system
water is kept in a narrow temperature range, a perma-
nent  manual  bypass  can  be  employed  and  manually
adjusted  to  achieve  an  inlet  temperature  of  105ºF
(41ºC)  or  higher. An  injector  pump  arrangement  may
also  be  utilized  to  keep  the  heater  loop  at  or  above
105ºF  (41ºC).  An  injector  pump  approach  has  the
added value of being able to adjust to changes in the
system water coming back to the heater take-off.
Temperature & Pressure Gauge
The  temperature  and  pressure  gauge  is  factory-
mounted in the in/out header.
Hydronic Heating
Pump Selection
In order to ensure proper performance of your heater
system, you must install a correctly sized pump. Ray-
pak recommends using a 20°F ∆T as design ∆T. (∆T is
the temperature difference between the inlet and out-
let water when the heater is firing at full rate). If a ∆T
of  larger  than  20°F  is  necessary,  see  Table  H  and
Table I for flow rate requirements.
Table H:  Heater Rates of Flow and Pressure Drops
10°F  T 
20°F  T 
30°F  T 
40°F  T 
Min. Flow 
Max Flow 
Model 
No.  gpm  P (ft)  gpm  P (ft)  gpm  P (ft)  gpm  P (ft)  gpm  P (ft)  T  gpm  P (ft)  T 
302B 
50 
3.3
25 
0.8 
N/A 
N/A 
N/A 
N/A 
20 
0.5 
25  90 
9.8 
402B 
67 
5.8
34 
1.4 
22 
0.6 
N/A 
N/A 
20 
0.5 
34  90 
10.0 
502B 
84 
9.1 
42 
2.3 
28 
1.1 
21 
0.6 
21 
0.6 
40  90 
10.4 
652B  N/A 
N/A 
55 
4.1 
36 
1.8 
27 
1.1 
27 
1.1 
40  90 
10.8  12 
752B  N/A 
N/A 
63 
5.7 
42 
2.6 
32 
1.5 
32 
1.5 
40  90 
11.3  14 
902B  N/A 
N/A 
76 
8.3 
50 
3.8 
38 
2.2 
38 
2.2 
40  90 
11.7  17 
Notes:
1.  Basis for minimum flow is 20 gpm or 40°F ∆T. Basis for maximum flow is 90 gpm. Flow switch will not operate if flow is less 
than 20 gpm.
2.  Rear-mounted pumps may provide higher flow rates on smaller models than the system requirements.
NOTE:  Individual  and  multi-boiler  Cold  Water  Start
systems require the use of a 20°F ∆T boiler pump.
NOTE:  To  ensure  proper  operation,  use  20°F  ∆T
boiler flow rates when designing the heating system
loop pump.