8. Locate and guard vent termination to prevent acci-
dental contact by people or pets.
9. DO NOT terminate vent in window well, stairwell,
alcove, courtyard or other recessed area.
10. DO  NOT  terminate  above  any  door,  window,  or
gravity air intake. Condensate can freeze, causing
ice formations.
11. Locate or guard vent to prevent condensate from
damaging  exterior  finishes.  Use  a  rust-resistant
sheet metal backing plate against brick or mason-
ry surfaces.
12. DO  NOT  extend  exposed  vent  pipe  outside  of
building. Condensate could freeze and block vent
pipe.
U.S. Installations
Refer  to  the  latest  edition  of  the  National  Fuel  Gas
Code.
Vent termination requirements are as follows:
1. Vent must terminate at least 4 ft below, 4 ft hori-
zontally  from  or  1  ft  above  any  door,  window  or
gravity air inlet to the building.
2. The vent must not be less than 7 ft above grade
when located adjacent to public walkways.
3. Terminate  vent  at  least  3  ft  above  any  forced  air
inlet located within 10 ft.
4. Vent must terminate at least 4 ft horizontally, and
in  no  case  above  or  below  unless  4  ft  horizontal
distance  is  maintained,  from  electric  meters,  gas
meters, regulators, and relief equipment.
5. Terminate  vent  at  least  6  ft  away  from  adjacent
walls.
6. DO NOT terminate vent closer than 5 ft below roof
overhang.
7. The  vent  terminal  requires  a  12  in.  vent  terminal
clearance from the wall.
8. Terminate vent at least 1 ft above grade, including
normal snow line.
9. Multiple  direct  vent  installations  require  a  4  ft
clearance between the ends of vent caps located
on the same horizontal plane.
Canadian Installations
Refer to latest edition of the B149 Installation code.
A vent shall not terminate:
1. Directly  above  a  paved  sidewalk  or  driveway
which is located between two single-family dwell-
ings and serves both dwellings.
2. Less than 7 ft (2.13 m) above a paved sidewalk or
paved driveway located on public property.
3. Within 6 ft (1.8 m) of a mechanical air supply inlet
to any building.
4. Above a meter/regulator assembly within 3 ft (915
mm)  horizontally  of  the  vertical  centre-line  of  the
regulator.
5. Within  6  ft  (1.8  m)  of  any  gas  service  regulator
vent outlet.
6. Less than 1 ft (305 mm) above grade level.
7. Within the 3 ft (915 mm) of a window or door which
can be opened in any building, any non-mechani-
cal  air  supply  inlet  to  any  building  or  the
combustion air inlet of any other appliance.
8. Underneath a verandah, porch or deck, unless the
verandah,  porch  or  deck  is  fully  open  on  a  mini-
mum  of  two  sides  beneath  the  floor,  and  the
distance  between  the  top  of  the  vent  termination
and the underside of the verandah, porch or deck
is greater than 1 ft (305 mm).
Changing the Flue Outlet
Follow  these  instructions  to  change  the  flue  connec-
tion  from  the  standard  top  location  to  the  rear  of  the
heater (when the optional vent tee is ordered).
1. Disconnect all electrical power from the heater (if
applicable).
2. Disconnect or isolate the main gas pipe from the
heater (if applicable).
3. Remove  the  screws,  gasket  and  dustcover  from
the rear of the heater.
4. Remove the screws, stainless steel flue cover and
gasket from the branch side of the tee located in
the flue box at the rear of the heater.