INSTALLATION
INSTALLATION
Installation Codes
Installations must follow these codes:
Local, state, provincial, and national codes, laws,
regulations and ordinances
National Fuel Gas Code, ANSI Z223.1/NFPA 54 –
latest edition (NFGC)
National  Electrical  Code,  ANSI/NFPA  70  -  latest
edition (NEC)
Standard  for  Controls  and  Safety  Devices  for
Automatically  Fired  Boilers,  ANSI/ASME  CSD-1,
when required (CSD-1)
For  Canada  only:  CAN/CSA  B149  Installation
Code  (B149)  and  CSA  C22.1  C.E.C.  Part  1
(C22.1)
The temperature of the water in the heater can be reg-
ulated by using the temperature controller. To comply
with  safety  regulations,  the  temperature  controller  is
set at the lowest setting when shipped from the facto-
ry.
To adjust the water temperature, insert a small straight
screwdriver into the adjustment screw on the front of
temperature  controller  and  turn  the  wheel  to  the
desired setting (See Fig. 4.).
CAUTION: Hotter  water  increases  the  risk  of
scalding! There is a hot water scald potential if the
thermostat is set too high.
Fig. 4: Temperature Controller
Equipment Base
The heater should be mounted on a level, structurally
sound surface. The heater is approved for installation
on  a  combustible  surface  but  must  NEVER  be
installed on carpeting. Gas-fueled equipment installed
in enclosed parking garages must be located at least
18 in. above the floor.
Stacking
Hi  Delta  units  can  be  stacked  two  units  high  with  an
optional stacking rack. A stacking kit is available from
Raypak for this type of installation.
CAUTION: The  heaters  should  be  located  in  an
area where water leakage will not result in damage
to  the  area  adjacent  to  the  appliances  or  to  the
structure. When such locations cannot be avoided, it
is  recommended  that  a  suitable  catch  pan,
adequately  drained,  be  installed  under  the
appliance. The pan must not restrict air flow.
REQUIRES OPTIONAL VENT TEE.
REQUIRES OPTIONAL VENT TEE IF VENTED OUT BACK 
OF HEATER.
Fig. 5: Typical Stacked Installation