ICP DAS USA DFS2H324J2A Manuel D’Utilisation

Page de 15
1
     CONTENTS
Page
51302618919-A   0606
SAFETY CONSIDERATIONS ................................ 1
GENERAL ........................................................... 1-4
INSTALLATION ................................................ 4-11
Indoor Unit Installation ........................................ 4
Outdoor Unit Installation ..................................... 6
Power Supply ....................................................... 7
Leak Test ............................................................... 7
Wiring Diagrams .............................................. 9-10
START-UP ........................................................... 11
System Checks ................................................... 11
CARE AND MAINTENANCE ............................... 11
Outdoor Units ..................................................... 11
Indoor Units ........................................................ 11
To Clean the Indoor Unit Front Panel ............... 11
To Clean Indoor Coil .......................................... 11
Air Filters for Indoor Units ................................ 11
SERVICE ............................................................. 11
TROUBLESHOOTING .................................... 12-15
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip-
ment can be hazardous due to system pressures, electrical compo-
nents, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should
install, start-up, and service this equipment.
Untrained personnel can perform basic maintenance func-
tions such as cleaning coils. All other operations should be per-
formed by trained service personnel.
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the equip-
ment.
Follow all safety codes. Wear safety glasses and work gloves.
Keep quenching cloth and fire extinguisher nearby when brazing.
Use care in handling, rigging, and setting bulky equipment.
Before installing or servicing system, always turn off main power
to system and install lockout tag on disconnect. There may be
more than one disconnect switch. Electrical shock can cause
personal injury.
GENERAL
These instructions cover the installation, start-up and servic-
ing of DFC2A/DFC2H outdoor and DFF2A/DFF2H indoor units cool-
ing only and heat pump duct free systems. See Table 1 for parts
included. See Tables 2 and 3 for Physical Data.
System Requirements
IMPORTANT: The Indoor units & the inter units cable
voltage is 30 VDC.
IMPORTANT: Each refrigerant line must be insulated
Separately. See line sizing requirements in tabel 2.
 •
Consult local building codes and National Electrical Code
(NEC, U.S.A.) for special installation requirements.
Max. cable length. Total voltage drop should not exceed 1V.
Therefore max. length:
For #18 AWG
24.3 Feet (7.4 m)
For #16 AWG
37.7 Feet (11.5 m)
For #14 AWG
50.0 Feet (18 m)
Use only type "G" or "C" fuses. Use single length power
cable without extension. Allow sufficient space for airflow
clearance on condensing units for wiring, refrigerant piping,
and servicing unit. See Fig. 1 and 2 for minimum required
distances between unit and walls or ceilings.
Indoor and outdoor units should be installed at a
Minimum length of 10 ft. apart.
Maximum line length of 50 ft. and
vertical separation of 30 ft.
Do not install indoor units near a direct source of heat such as
direct sunlight, steam or flame.
Do not bury more than 36 in. of refrigerant pipe in the ground. If
any section of pipe is buried, there must be a 6 in. vertical rise to
the valve connections on the outdoor units. If more than the rec-
ommended length is buried, refrigerant may migrate to the cooler
buried section during extended periods of system shutdown. This
causes refriger-ant slugging and could possibly damage the com-
pressor at start-up.
 WARNING
Pg 1
 CAUTION
 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without inc.          Printed in Israel
Fig. 1 — 38BCC/BCQ 018, 024 Outdoor Unit Clearances
 Installation, Start-Up and Service Instructions
DFS2A/H  2 X 09, 2 X 12
Duct Free Systems
Cooling Model
DFS2A318J2A
DFS2A324J2A
Heat Pump
DFS2H318J2A
DFS2H324J2A
LEFT (min.)
6" (0.15m)
TOP (min.)
2" (0.6m)
REAR (min.)
6" (0.15m)
RIGHT (min.)
2" (0.6m)
FRONT (min.)
2" (0.6m)
R-22