MECHANICAL SPECIFICATIONS
GENERAL DESCRIPTION
Units shall be factory-assembled, single packaged, Electric 
Cooling units, designed for outdoor mounted installation. ACP 
units shall have minimum SEER ratings of 13. They shall have 
built in, equal size, field convertible duct connections for down 
discharge supply/return or horizontal discharge supply/return.
The units shall be factory wired, piped, charged with R-22 
refrigerant and factory tested prior to shipment. All unit wiring 
shall be both numbered and color coded.
All units shall be manufactured in a facility certified to ISO 9001 
standards, and the cooling performance shall be rated in 
accordance with DOE and ARI test procedures. Units shall be 
certified to UL 1995/CAN/CSA C22.2 No. 236 standard.
UNIT CABINET
1.
Unit cabinet shall be constructed of galvanized steel, with 
exterior surfaces coated with a non-chalking, powered 
paint finish, certified at 1000 hours salt spray test per 
ASTM-B117 standards.
2.
The unit top shall be a single piece “Water Shed” design, 
with drip edges and no-seam corners to provide optimum 
water integrity.
3.
Unit shall have a rigidly mounted condenser coil guard to 
provide protection from objects and personnel after 
installation.
4.
Indoor blower section shall be insulated with up to 3/4” 
thick, aluminum, foil faced insulation, fastened to prevent 
insulation from entering the air stream.
5.
Cabinet panels shall be “large” size, easily removable for 
servicing and maintenance, with built-in lift handles.
6.
Unit shall be built on a formed, “Super-Structure” design 
base pan, with embossments at critical points to add 
strength, rigidity and aid in minimizing sound.
7.
Full perimeter base rails shall be provided to assure 
reliable transit of equipment, overhead rigging, fork truck 
access and proper sealing on roof curb applications. Base 
rails shall be removable, when required, to lower unit 
height.
8.
Filters shall be furnished and be accessible through a 
removable access door, sealed air tight. (Single phase 
models - accessory kit available. Three phase models - 
standard from factory.)
9.
Units vertical discharge and return duct configuration shall 
be designed to fit between standard 24” O.C. beams 
without modification to building structure, duct work and 
base unit.
10. Condensate pan shall be internally sloped and conform to 
ASHARE 62-89 self-draining standards, with ¾” NPTI 
copper, ridged mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
1.
The ACP fan motor shall be direct drive, 5 speed design.
2.
Fan wheel shall be double-inlet type with forward-curved 
blades, dynamically balanced to operate smoothly 
throughout the entire range of operation. Airflow design 
shall be constant air volume.
3.
Bearings shall be sealed and permanently lubricated for 
longer life and no maintenance.
4.
Fan assembly shall be “Slip Track” (slide-out) design for 
easy removal and cleaning.
OUTDOOR (CONDENSER) FAN ASSEMBLY
1.
The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to 
corrosion resistant steel spider bracket and shall be 
statically balanced for smooth operation.
2.
The outdoor fan motor shall be totally enclosed with 
permanently lubricated bearings and internally protected 
against overload conditions.
REFRIGERANT COMPONENTS
1.
Compressors:
a. Shall be fully hermetic reciprocating type, direct drive,
internally protected with internal high-pressure relief and
over temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or -
10% of the unit nameplate voltage.
b Shall have internal isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
2.
Coils:
a. Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally-
enhanced copper tubes with all joints brazed.
b Evaporator and Condenser coils shall be of the direct
expansion, draw-thru design.
3.
Refrigerant Circuit and Refrigerant Safety Components 
shall include:
a. Independent fixed-orifice or balanced port bi-flow TXV
expansion devices.
b. Filter/strainer to eliminate any foreign matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge and without
disrupting condenser or evaporator air flow.
d The refrigeration system shall provide at least 10° F of
liquid sub-cooling at design conditions.
4.
Unit Controls: