Johnson Controls 340968-XIM-A-0108 Manuel D’Utilisation

Page de 24
340968-XIM-A-0108
Johnson Controls Unitary Products
23
TYPICAL WIRING DIAGRAM NOTES
1.
All field wiring to be accomplished following city, local 
and/or national codes in effect at time of installation of 
this unit.
2.
Caution: Label all wires prior to disconnection when ser-
vicing controls. Wiring errors can cause improper and 
dangerous operation. If any of the wire as supplied with 
this unit must be removed it must be replaced with type 
105°C, 600V wire or equivalent clearly renumbered for 
identification. Verify proper operation after servicing.
3.
Motors inherently protected.
4.
Factory wired for 230V. For 208V operation, move wire 
107/PR to 208V. Tap on transformer T1
5.
See unit nameplate for maximum fuse size and/or circuit 
breaker size and minimum circuit ampacity.
6.
If both LR and ASCT are present, wire 801/BL and 805/
BL are connected to ASCT-3. If only LR is present wire 
801/BL and 805/BL are connected to M1 coil. If only 
ASCT is present wire 202/Y is connected to ASCT-3. If 
neither LR or ASCT are present, wire 202/Y is connected 
to M1 coil as shown.
7.
Shunt contact also used with crankcase heater. 
(optional)
8.
Select indoor blower speed to remain within the temper-
ature rise range on the nameplate in heating.
FIGURE 15 -  TYPICAL WIRING DIAGRAM LEGEND
Open all disconnects before servicing this unit.
LEGEND
ALS
AUXILARY LIMIT SWITCH
ASCT
ANTI-SHORT CYCLE TIMER (OPTIONAL)
BR
BLOWER RELAY
CB
CIRCUIT BREAKER
CCH
CRANK CASE HEATER (OPTIONAL)
COMPR
COMPRESSOR
DM
DRAFT MOTOR
FCB
FAN CONTROL BOARD
GND
GROUND
FS
FREEZE STAT SWITCH (OPTIONAL)
HP
HIGH PRESSURE SWITCH OPENS @ 380 PSIG
IDFAN
INDOOR FAN MOTOR
LP
LOW PRESSURE SWITCH OPENS @ 7 PSIG
LS
LIMIT SWITCH
LR
LOCK OUT RELAY (OPTIONAL)
M1
CONTACTOR, COMPR. AND OD FAN
ODFAN
OUTDOOR FAN MOTOR
PS
PRESSURE SWITCH
RC1 / RC2
COMPRESSOR START & OUTDOOR FAN RUN CAPACITOR
RS
ROLLOUT SWITCH
TB4
TERMINAL BLOCK
T1
TRANSFORMER, 24V, 230V