NOTE 1: HACR Type per NEC.
TABLE 19: J**DJ ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET (CONTINUED)
MODEL
(TON-
NAGE)
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID 
BLOWER 
MOTOR 
FLA
CONV
OUTLET 
AMPS
HEATER OPTION
MIN.
CIRCUIT
 AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL
KW
STAGES
AMPS
J20
(20)
208
33.6
225
3.7
20.0
0.0
None
0.0
~
~
110.4
125
E18
13.5
1
37.5
110.4
125
E36
27.0
2
75.1
118.7
125
E54
40.6
2
112.6
165.9
175
E72
54.1
2
150.1
175.2
200
230
33.6
225
3.7
20.0
0.0
None
0.0
~
~
110.4
125
E18
18.0
1
43.3
110.4
125
E36
36.0
2
86.6
133.3
150
E54
54.0
2
129.9
154.9
175
E72
72.0
2
173.2
198.2
225
460
17.3
114
1.9
10.0
0.0
None
0.0
~
~
56.5
70
E18
18.0
1
21.7
56.5
70
E36
36.0
2
43.3
66.6
70
E54
54.0
2
65.0
77.5
90
E72
72.0
2
86.6
99.1
110
575
13.5
80
1.5
8.2
0.0
None
0.0
~
~
44.6
50
E18
18.0
1
17.3
44.6
50
E36
36.0
2
34.6
53.6
60
E54
54.0
2
52.0
62.2
70
E72
72.0
2
69.3
79.5
90
J25
(25)
208
47.1
245
3.7
38.6
0.0
None
0.0
~
~
159.4
200
E18
13.5
1
37.5
159.4
200
E36
27.0
2
75.1
159.4
200
E54
40.6
2
112.6
189.1
200
E72
54.1
2
150.1
198.4
225
230
47.1
245
3.7
38.6
0.0
None
0.0
~
~
159.4
200
E18
18.0
1
43.3
159.4
200
E36
36.0
2
86.6
159.4
200
E54
54.0
2
129.9
178.2
200
E72
72.0
2
173.2
221.5
250
460
19.6
125
1.9
19.3
0.0
None
0.0
~
~
71.0
90
E18
18.0
1
21.7
71.0
90
E36
36.0
2
43.3
78.3
90
E54
54.0
2
65.0
89.1
100
E72
72.0
2
86.6
110.7
125
575
15.8
100
1.5
15.4
0.0
None
0.0
~
~
57.0
70
E18
18.0
1
17.3
57.0
70
E36
36.0
2
34.6
62.6
70
E54
54.0
2
52.0
71.2
80
E72
72.0
2
69.3
88.5
100