9. ELECTRICAL DATA
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
230 - 208 V / 1 phase / 60 Hz
230 - 208 V / 1 phase / 60 Hz
Rating conditions
A
0.9 - 0.8
1.8 - 1.8
18.1 - 18.5
20.8 - 21.1
kW
0.2 - 0.16
0.36 - 0.34
3.67 - 3.62
4.23 - 4.12
Full load conditions
A
0.9 - 0.8
1.8 - 1.8
21.44 - 22.7
24.1 - 25.3
kW
0.2 - 0.16
0.36 - 0.34
4.49 - 4.48
5.05 - 4.98
Starting amperes
A
1 - 1
2 - 2
131 - 131
134 - 134
Electrical characteristics
Indoor model: XS4232 / Outdoor model: C4232, CL4232
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
230 - 208 V / 1 phase / 60 Hz
230 - 208 V / 1 phase / 60 Hz
Rating conditions
A
0.7 - 0.7
1.8 - 1.8
18.1 - 18.5
20.6 - 21.0
kW
0.16 - 0.14
0.36 - 0.34
3.67 - 3.62
4.19 - 4.10
Full load conditions
A
0.7 - 0.7
1.8 - 1.8
21.44 - 22.7
23.9 - 25.2
kW
0.16 - 0.16
0.36 - 0.34
4.49 - 4.48
5.01 - 4.96
Starting amperes
A
1 - 1
2 - 2
131 - 131
134 - 134
Rating Conditions
: Indoor Air Temperature
80 
°
F DB / 67 
°
F WB
Outdoor Air Temperature
95 
°
F DB
Full Load Conditions : Indoor Air Temperature
80 
°
F DB / 67 
°
F WB
Outdoor Air Temperature 115 
°
F DB
Indoor model: TS4232 / Outdoor model: C4232, CL4232