Emerson 2 Manuel D’Utilisation

Page de 56
Specifications
26
Table 13
Electrical data, 50 Hz - amps
Model
Volts
Phase
No Heat
5 kW Heat
10 kW Heat
15 kW Heat*
Circ1
Circ2
FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
ET017H 220/240
1
12.8 15.1
20
23.4 29.3
30
44.4 55.5
60
NA
ET017S 220/240
1
13.8 16.3
25
23.4 29.3
30
44.4 55.5
60
NA
ET023H 220/240
1
13.7 16.2
25
23.4 29.3
30
44.4 55.5
60
NA
ET023S 220/240
1
15.2 18.1
30
23.4 29.3
30
44.4 55.5
60
NA
ET023H 380/415
3
5.9
6.9
15
8.3
10.4
15
15.3 19.1
20
NA
ET023S 380/415
3
6.3
7.4
15
8.3
10.4
15
15.3 19.1
20
NA
ET035H 220/240
1
20.3 24.4
40
23.4 29.3
40
44.4 55.5
60
44.4 55.5
60
21
26.3
30
ET035S 220/240
1
17.4 20.8
35
23.4 29.3
35
44.4 55.5
60
44.4 55.5
60
21
26.3
30
ET035H 200/230
3
15.2 18.1
30
15.2 18.1
30
26.4
33
35
38.4
48
50
ET035S 200/230
3
14.5 17.2
25
14.5
18
25
26.4
33
35
38.4
48
50
ET035H 380/415
3
6.8
8
15
8.3
10.4
15
15.3 19.1
20
22.3 27.9
30
ET035S 380/415
3
7.7
9.1
15
8.3
10.4
15
15.3 19.1
20
22.3 27.9
30
ET047S
ET347S 200/230
3
21.9 25.5
35
21.9 25.5
35
28.2 35.3
35
40.2 50.3
60
ET047S
ET347S
380/415
3
11
12.8
20
11
12.8
20
16.1 20.1
25
23.1 28.9
30
EF059S
ET359S 200/230
3
28.3 33.5
50
28.3 33.5
50
28.3 35.3
50
40.2 50.3
50
ET059S
ET359S 380/415
3
13.8 16.3
25
13.8 16.3
25
16.1 20.1
20
23.1 28.9
30
* 15 kW heat option @ 220/240 - 1 phase requires two electrical feeds.
Circuit 1 supplies the compressor, condenser, 10 kW heat and the evaporator motor.
Circuit 2 supplies the remaining 5 kW heat.