Goodman Mfg SS-CPG180-240 Manuel D’Utilisation

Page de 20
p
rodUCT
 s
peCifiCaTions
p
rodUCT
 s
peCifiCaTions
4 www.goodmanmfg.com 
SS-CPG180-240
p
rodUCT
 s
peCifiCaTions
 — 15 T
ons
CPG180350
3B***
CPG180350
4B***
CPG180***
7B***
Cooling Capacity
Total, BTU/h
180,000
180,000
180,000
Sensible BTU/h
127,500
127,500
127,500
EER / IEER
10.8 / 11
10.8 / 11
10.8 / 11
Decibels
88
88
88
ARI Reference #s
3965698
3965698
3965698
Heating Capacity
Max. Input:  High / Low  KBTU/h
350 / 262 
350 / 262 
350 / 262 
Output: High / Low KBTU/h 
280 / 210
280 / 210
280 / 210
Steady State Efficiency (%)
80
80
80
Temperature Rise: High / Low (°F)
30-60 / 20-50
30-60 / 20-50
30-60 / 20-50
No. of Burners
7
7
7
Evapoartor Motor / Coil
Motor Type (Belt Drive)
Std Static
Std Static
Std Static
Indoor Nominal CFM
5,400
5,400
5,400
Indoor Motor FLA (Cooling)
12.7
6.4
5.1
Horsepower - RPM
5.0 - 1,725
5.0 - 1,725
5.0 - 1,725
Metering Device 
TXV
TXV
TXV
Filter Size (#)
 20 x 25 x 2 (6)
 20 x 25 x 2 (6)
 20 x 25 x 2 (6)
Drain Size (NPT)
1"
1"
1"
R-410A Refrigerant Charge Cir #1 & 2
290 oz.
290 oz.
290 oz.
Evaporator Coil Face Area (ft²)
20
20
20
Rows Deep / Fins per Inch
4 / 16
4 / 16
4 / 16
Belt Drive Evap Fan Data
# of Wheels (D x W)
2 (15" x 12")
2 (15" x 12")
2 (15" x 12")
Motor Sheave
1VP50 x 1⅛"
1VP50 x 1⅛"
1VP50 x 1⅛"
Blower Sheave / Belt 
BK90 x 1³/₁₆" / BX42
BK90 x 1³/₁₆" / BX42
BK90 x 1³/₁₆" / BX42
Condenser Fan / Coil
Quantity of Condenser Fan Motors
3
3
3
Horsepower - RPM
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
Fan Diameter / # Fan Blades
22 / 3
22 / 3
22 / 3
Outdoor Nominal CFM
7,200
7,200
7,200
Face Area (ft²)
53.3
53.3
53.3
Rows Deep / Fins per Inch
2 / 18
2 / 18
2 / 18
Compressor
Quantity / Type
2 / Scroll
2 / Scroll
2 / Scroll
Compressor RLA / LRA CIR. #1
25 / 164
12.2 / 100
9.0 / 78
Compressor RLA / LRA CIR. #2
29.5 / 195
14.7 / 95
12.2 / 80
Electrical Data / Static
Voltage / Phase / Frequency
208-230/3/60
460/3/60
575/3/60
Standard Max Static
1.2
1.2
1.2
Outdoor Fan FLA / LRA
2.4 / 5.2
1.2 / 2.6
.9 / 2.2
Total Unit Amps
74.4
36.9
29
Min. Circuit Ampacity¹
81.8
40.6
32.1
Max. Overcurrent Protection (amps)²
100
50
40
Entrance Power Supply
2⅛"
2⅛"
2⅛"
Entrance Control Voltage
⅞"
⅞"
⅞"
Operating Weight (lbs)
2155
2155
2155
Ship Weight (lbs)
2270
2270
2270
¹  Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
²   May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.