Installation Instructions
INSTALL THE OUTDOOR UNIT 
• Install the connection tube
1. Align the center of the tubing flare with the
relevant valve.
2. Screw in the flare nut by hand and then tighten
the nut with spanner and torque wrench. See
the table below for the correct torque.
3. Connecting tube specifications are shown
below:
NOTE: Exceeding tightening torque will damage
the copper tubing.
NOTE: To prevent wind and pest infiltration, 
seal holes around the tubing and wiring with 
the supplied sealer.
10
PURGE THE AIR AND 
TEST FOR LEAKAGE 
1. Install the connecting tubes of the 
indoor/outdoor unit.
2. DO NOT OPEN THE GAS VALVES UNTIL THE
EVACUATION PROCESS IS COMPLETE.
3. Remove the gas line service port cap and
connect the gas valves of the vacuum gauge,
vacuum pump and outdoor unit.
NOTE: Connect by using a 1/4
Female x 
1/2
Male Adapter Access Fitting (obtain locally).
4. Start the vacuum pump. (Running time should 
be more than 15 minutes.)
5. Check the vacuum with the vacuum gauge. The
gauge should read -30 in. Hg. After evacuation,
fully close the handle on the manifold valve 
(on the vacuum pump device). Then stop the
vacuum pump and disconnect it.
6. The pressure should be kept for 1–2 minutes 
to confirm that the reading of the vacuum 
gauge does not change. The pressure should 
be -30 in. Hg.
7. Remove the vacuum line and replace the service 
port cap. 
8. Remove both the liquid and gas valve caps.
9. Open the gas and liquid valve entirely, using 
the 5 mm Allen wrench. If this is not done, the
performance will be reduced, or an error will
occur.
10. Replace the caps and tighten securely. 
11
Cap
Liquid tube
Gas tube
Vacuum pump
Vacuum gauge
INSTALLATION (cont.)
2
Tubing OD
Tightening torque (in./lb.)
1/4
140–170
3/8
270–310
1/2
440–480
5/8
530–570
Tightening torque table
Torque wrench
Flare nut
Joint
Spanner
10,000/14,000
20,000
Specifications
BTU Units
BTU Units
Design Length
20 ft.
26.2 ft.
Extra Refrigerant Charge
0.16 oz./ft.
0.54 oz./ft.
Per Ft. Above Design Length
Outer Diameter Liquid Pipe
1/4
3/8
Outer Diameter Gas Pipe
1/2
5/8
Max. Distance Height
33 ft.
33 ft.
Max. Distance Length
68 ft.
98 ft.