Heat Controller CDG SERIES Manuel D’Utilisation

Page de 13
Cased/Uncased Coils 
INSTALLATION INSTRUCTIONS
 
Heat Controller, Inc.
9
Drain pan has two drain connections on each side to provide flexibility of connection and drainage. Make 
sure pan has proper pitch and plugged if second connection is not used.
It is highly recommended to use the secondary drain line to prevent overflow when the primary drain is 
plugged.
NOTE: Water coming from this line means the coil primary drain is plugged and needs clearing.
Install a trap in the drain line below the bottom of the drain pan (required). If using a copper drain line, 
solder a short piece of pipe to the connector before installing a drain fitting. DO NOT over torque the 3/4” 
copper connector to the plastic drain connection. Use a wet rag or heatsink material on the short piece to 
protect plastic drain pan, complete the drain line installation (Fig.5). Use (Fig.6) as a template for typical 
drain pipe routing. This figure shows how to avoid interference with vent piping.
CONDENSATE DRAIN TRAP
Unit
DO NOT OVERTIGHTEN DRAIN FITTING
TOWARD DRAIN CONNECTION 
UNIT MUST BE SLIGHTLY INCLINED
 
3"
3"
TO
 
APPROVED DRAIN
DO NOT OPERATE UNIT WITHOUT 
CONDENSATE DRAIN TRAP.
secondary
primary
secondary
primary
Fig. 5: Drain Line Installation
Fig. 6: Drain Pipe Routing