Toshiba RAV-SM1406BT-TR Manuel D’Utilisation

Page de 104
– 35 –
Indoor P.C. Board Optional Connector Specifications (MCC-1631)
Function
Connector No.
Pin No.
Specification
Remarks
Fan output
CN32
1
DC12 V
Factory default setting: ON when indoor unit in 
operation and OFF when indoor unit at rest
* Fan can be operated on its own by pressing FAN 
button on remote controller (DN = 31)
2
Output
HA
CN61
1
Start / stop input
Start / stop input for HA (J01: In place / Removed = 
Pulse input (factory default) / Step input)
2
3
Remote controller disabling 
input
Enables / disables start / stop control via remote 
controller
4
In-operation output
ON during operation (HA answerback signal)
5
DC12 V (COM)
6
Alarm output
ON while alarm ON
Optional 
output
CN60
1
DC12 V (COM)
2
Defrosting output
ON while outdoor unit defrosted
3
Thermostat ON output
ON while real thermostat ON (compressor ON)
4
Cooling output
ON while air conditioner in cooling or related operation 
(COOL, DRY or cooling under AUTO mode)
5
Heating output
ON while air conditioner in heating operation (HEAT or 
heating under AUTO mode)
6
Fan output
ON while indoor fan ON (air cleaner in use or via 
interlock wiring)
External error 
input
CN80
1
DC12 V (COM)
Generates test code L30 and automatically shuts down 
air conditioner (only if condition persists
for 1 minute)
2
DC12 V (COM)
3
External error input
CHK
Operation 
check
CN71
1
Check  mode  input
Used for indoor operation check (prescribed operational 
status output, such as indoor fan "H" or drain pump ON, 
to be generated without communication with outdoor 
unit or remote controller)
2
0 V
0 V
DISP
Display mode
CN72
1
Display mode input
Product display mode - Communication just between 
indoor unit and remote controller enabled (upon turning 
on of power) Timer short-circuited out (always)
2
0 V
EXCT
Demand
CN73
1
Demand input
Imposes thermostat OFF on indoor unit
2
0 V (COM)