The LEDs and DIP switches are 
located on the lower left of the P.C. 
board of the outdoor unit.
No.
Cause
Display mode 1
Display mode 2
D800 D801 D802 D803 D804 D800 D801 D802 D803 D804
1
Normal
2
Discharge (TD) sensor error
3
Heat exchanger (TE) sensor error
4
Heat exchanger (TL) sensor error
5
Outside air temperature (TO) sensor error
6
Suction (TS) sensor error
7
Heat sink (TH) sensor error
8
Outdoor temperature sensor (TE/TS) connection error
9
Outdoor EEPROM error
10
Compressor lock
11
Compressor lock
12
Current detection circuit error
13
Thermostat for compressor activated
14
Model data not set (on the service P.C. board)
15
MCU-MCU communication error
16
Discharge temperature error
17
Abnormal power (open phase detected or abnormal voltage)
18
Heat sink overheat
19
Gas leak detected
20
4-way valve reverse error
21
High pressure release operation
22
Outdoor fan motor error
23
Compressor driver short-circuit protection
24
Position detection circuit error in one-line display
25
Ps sensor error
26
Ps drop down error
SW800 SW801 SW806
SW802
SW803
LED
ON
1
2
3
4
ON
1
2
3
4
SW804
SW805
ON
1
2
3
4
ON
1
2
3
4
D805
D804
D803
D802
D801
D800
D805
D804
D803
D802
D801
D800
Enlarged view of 
LEDs
24
EN
Digital Inverter
15
APPENDIX 
Work instructions
The existing R22 and R407C piping can be reused for our 
digital inverter R410A product installations. 
WARNING
Confirming the existence of scratches or dents on the 
existing pipes and confirming the reliability of the pipe 
strength are conventionally referred to the local site.
Basic conditions needed to reuse existing pipes
Check and observe the presence of three conditions in the 
refrigerant piping works.
1. Dry (There is no moisture inside of the pipes.) 
2. Clean (There is no dust inside of the pipes.) 
3. Tight (There are no refrigerant leaks.) 
Restrictions for use of existing pipes
In the following cases, the existing pipes should not be 
reused as they are. Clean the existing pipes or exchange 
them with new pipes.
1. When a scratch or dent is heavy, be sure to use new 
pipes for the refrigerant piping works.
2. When the existing pipe thickness is thinner than the 
specified “Pipe diameter and thickness,” be sure to use 
new pipes for the refrigerant piping works.
• The operating pressure of R410A is high (1.6 times 
that of R22 and R407C).  If there is a scratch or dent on 
the pipe or a thinner pipe is used, the pressure strength 
may be inadequate, which may cause the pipe to break 
in the worst case.
*
Pipe diameter and thickness (mm) 
3. When the outdoor unit was left with the pipes 
disconnected, or the gas leaked from the pipes and the 
pipes were not repaired and refilled.
• There is the possibility of rain water or air, including 
moisture, entering the pipe.
4. When refrigerant cannot be recovered
• There is the possibility that a large quantity of dirty oil 
or moisture remains inside the pipes.
5. When a commercially available dryer is attached to the 
existing pipes
• There is the possibility that copper green rust has been 
generated.
6. When the existing air conditioner is removed after 
refrigerant has been recovered.
Check if the oil is judged to be clearly different from 
normal oil.
• The refrigerator oil is copper rust green in color:
There is the possibility that moisture has mixed with the 
oil and rust has been generated inside the pipe.
• There is discolored oil, a large quantity of residue, or a 
bad smell.
• A large quantity of shiny metal dust or other wear 
residue can be seen in the refrigerant oil.
7. When the air conditioner has a history of the compressor 
failing and being replaced.
• When discolored oil, a large quantity of residue, shiny 
metal dust, or other wear residue or mixture of foreign 
matter is observed, trouble will occur.
8. When temporary installation and removal of the air 
conditioner are repeated such as when leased etc.
9. If the type of refrigerator oil of the existing air conditioner 
is other than the following oil (Mineral oil), Suniso, Freol-
S, MS (Synthetic oil), alkyl benzene (HAB, Barrel-freeze), 
ester series, PVE only of ether series.
• The winding-insulation of the compressor may 
deteriorate.
NOTE
The above descriptions are results have been confirmed by 
our company and represent our views on our air 
conditioners, but do not guarantee the use of the existing 
pipes of air conditioners that have adopted R410A in other 
companies.
Branching pipe for simultaneous operation system
In the concurrent twin system, when TOSHIBA has 
specified that branching pipe is to be used, it can be 
reused.
Branching pipe model name: 
RBC-TWP30E2, RBC-TWP50E2, RBC-TRP100E 
On the existing air conditioner for simultaneous operation 
system (twin, triple, double twin system), there are cases 
of branch pipes being used that have insufficient 
compressive strength.
In such case, please change the piping to a branch pipe 
for R410A. 
Curing of pipes
When removing and opening the indoor or outdoor unit for a 
long time, cure the pipes as follows:
Otherwise rust may be generated when moisture or 
foreign matter due to condensation enters the pipes.
The rust cannot be removed by cleaning, and new pipes 
are necessary. 
Reference outside 
diameter (mm)
Wall thickness 
(mm) 
Material
6.4
0.8
9.5
0.8
12.7
0.8
15.9
1.0
19.1
1.2
22.2
1.0
Half hard
28.6
1.0
Half hard
Placement location
Term
Curing manner
Outdoors
1 month or more
Pinching
Less than 1 month
Pinching or taping 
Indoors
Every time