Refrigeration Lines
1
/
4
inch O/D copper “liquid line” and a ½ inch O/D copper “suction line” connect the two units.
The refrigerant drier and sight glass shall be installed in that order in direction of refrigerant flow 
in the liquid line between the condensing unit and evaporator. Enclose the suction line in a cellular 
insulation ½” wall thickness Armaflex (brand name) or equal to reduce heat transfer.
Wiring System
The compressor is controlled by a “pump down cycle,” therefore, no wiring between the condensing 
unit and evaporator unit is necessary. Wire the system in accordance with local codes and the 
enclosed  wiring  diagrams  (Evaporator  wiring  on  pg  17,  schematics  below,  and  on  pg  20).  The 
evaporator unit requires a standard 15 amp circuit, non-GFI. A dedicated circuit is not mandatory, 
but recommended.