Parameter Description and Options
TABLE 7-1 – DEFINITIONS (CONTINUED)
Continued on next page
MENU ITEM
DEFINITION
COMP 2 OUTPUT
THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE 
UNIT CONTROLLER TO COMPRESSOR CIRCUIT 2
COMP 2 OVERLOAD SWITCH
THIS IS THE STATUS OF THE BINARY INPUT FROM THE 
COMPRESSOR OVERLOAD FOR COMPRESSOR SYSTEM 2 TO 
THE UNIT CONTROLLER.  ON - OKAY, OFF - FAULTED.
COMP 3 ASCD ACTIVE
THIS IS USED TO DETERMINE THE STATUS OF THE OFF CYCLE 
TIMER.  ON MEANS THE COMPRESSOR 3 IS IN THIS MODE
COMP 3 ASCD TIMER
THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR 
COMPRESSOR 3 IN SECONDS.
COMP 3 MIN RUN TIME
THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME FOR 
COMPRESSOR 3 IN SECONDS.
COMP 3 OUTPUT
THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE 
UNIT CONTROLLER TO COMPRESSOR CIRCUIT 3
COMP 3 OVERLOAD SWITCH
THIS IS THE STATUS OF THE BINARY INPUT FROM THE 
COMPRESSOR OVERLOAD FOR COMPRESSOR SYSTEM 3 TO 
THE UNIT CONTROLLER.  ON - OKAY, OFF - FAULTED.
COMP 4 ASCD ACTIVE
THIS IS USED TO DETERMINE THE STATUS OF THE OFF CYCLE 
TIMER.  ON MEANS THE COMPRESSOR 4 IS IN THIS MODE
COMP 4 ASCD TIMER
THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR 
COMPRESSOR 4 IN SECONDS.
COMP 4 MIN RUN TIME
THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME FOR 
COMPRESSOR 4 IN SECONDS.
COMP 4 OUTPUT
THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE 
UNIT CONTROLLER TO COMPRESSOR CIRCUIT 4
COMP 4 OVERLOAD SWITCH
THIS IS THE STATUS OF THE BINARY INPUT FROM THE 
COMPRESSOR OVERLOAD FOR COMPRESSOR SYSTEM 4 TO 
THE UNIT CONTROLLER.  ON - OKAY, OFF - FAULTED.
COMPRESSOR #1 ACCUMULATED RUNTIME
THIS IS THE NUMBER OF HOURS THAT COMPRESSOR SYSTEM 
1 HAS BEEN OPERATIVE
COMPRESSOR #2 ACCUMULATED RUNTIME
THIS IS THE NUMBER OF HOURS THAT COMPRESSOR SYSTEM 
2 HAS BEEN OPERATIVE
COMPRESSOR #3 ACCUMULATED RUNTIME
THIS IS THE NUMBER OF HOURS THAT COMPRESSOR SYSTEM 
3 HAS BEEN OPERATIVE
COMPRESSOR #4 ACCUMULATED RUNTIME
THIS IS THE NUMBER OF HOURS THAT COMPRESSOR SYSTEM 
4 HAS BEEN OPERATIVE
COMPRESSORS AVAILABLE FOR COOLING
THIS PARAMETER IDENTIFIES THE NUMBERS OF COMPRESSOR 
THE UNIT CONTROLLER IS SET UP TO CONTROL
CONDENSER FAN #1 OUTPUT
THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE 
UNIT CONTROLLER TO THE #1 CONDENSER FAN, OFF OR ON
CONDENSER FAN #2 OUTPUT
THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE 
UNIT CONTROLLER TO THE #2 CONDENSER FAN, OFF OR ON
CONTINUOUS INDOOR FAN OPERATION WITH 
SENSOR
WHEN THIS PARAMETER IS TURNED ON, ON A CONSTANT 
VOLUME UNIT THE SUPPLY FAN WILL OPERATE WHENEVER 
THE UNIT IS IN THE OCCUPIED MODE
CONTROL IN COMFORT VENTILATION
THIS IDENTIFIES IF THE UNIT CONTROLLER IS IN THE COMFORT 
VENTILATION MODE.  OFF NOT IN MODE, ON IN COMFORT 
VENTILATION MODE.