York TCGD12 THRU 60 Manuel D’Utilisation

Page de 18
400034-YTG-B-0708
4
Johnson Controls Unitary Products
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter-
connecting line tubing.
2. Verify the TXV or orifice and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical 
Data Table.
4. For TXV match charge weight needs to be weighed in for specififc coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for 
evaporator + adder for line set.
AHP18B3X 
41  +  0 
52  +  0 
AHP24B3X
52  +  0 
AHP30B3X 
61  +  3 
65  +  4 
AHP36C3X 
73 + 4 
AHP42C3X 
73 + 4 
81 + 0 
AHP/SHP60D3X –
84 
AV24B3X 
52  +  2 
AV36C3X 
61 + 7 
65 + 12 
73 + 4 
AV/SV48D3X –
84 
F4FP024    
52  +  0 
2A  +  0 
F4FP036    
61  +  1 
2A  +  2 
F4FP040    
65  +  0 
2A  +  0 
F5FP048    
73 + 0 
81 + 5 
84 + 2 
2A + 0 
2C + 5 
2C + 2 
F5FP060    
84  +  0 
2C  +  0 
F4FV060    
84  +  0 
2C  +  0 
FOOTNOTES:
1. For applications requiring a TXV use 1TVM series kit.
2. Approved orifice shipped with outdoor unit.
3. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 
2FD06700224.
4. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
Additional R-22 Charge / Orifice Size for Various Matched Systems (Continued)
Outdoor Unit 
TCGD12
S21S2(H)
TCGD18
S21S2(H)
TCGD24
S21S2(H)
TCGD30
S21S2(H)
TCGD36
S21S2(H)
TCGD42
S21S2(H)
TCGD48
S21S2(H)
TCGD60
S21S2
Required Orifice or TXV 
1,2
0.041 / 2A 
0.052 / 2A  0.059 / 0.061 / 2A  0.065 / 2A 
0.073 / 2A 
0.081 / 2C 
0.084 / 2C 
0.096 / 2C
Factory R-22 Charge, lbs-oz
3 - 2
3 - 0
3 - 13
3 - 7
3 - 15
4 - 2
4 - 5
5 - 4
Indoor Coil
3,4
Additional Charge, Oz
See  Caution below   
See  Caution below   
See  Caution below   
See  Caution below   
See  Caution below   
See  Caution below   
Models 12-48 require start kits for TXV matches. Models with “H” on the end of the model number have factory installed start kits.
For models without an “H” refer to tech guide for kit number reference.
F*FP Air Handlers come with a factory installed R-22 TXV. Please note that some models may take a different TXV then what is factory
installed. The proper TXV must be installed for system reliability and performance. Also note, TXV must be removed for orifice match.