7
actuators have an adjustable auxiliary end-switch for 
optional power exhaust control.
• VAV or Simplicity® Intelli-Comfort™ control, a 
factory-installed dry bulb sensor determines if outdoor 
air temperature is low enough to provide free-cooling 
operation. (Field-installed humidity sensors for either 
outdoor air or outdoor & return air streams are available 
for single enthalpy and differential enthalpy 
configurations, respectively.)
• Slab Economizer for Energy Recovery Ventilators
(With barometric relief and Fresh Air Hood) - The 
economizer is provided with a single enthalpy input. The 
economizer is 2% low leakage type, and is shipped 
installed and wired. The economizer has spring return, 
fully modulating damper actuators and is capable of 
introducing up to 100% outdoor air. As the outdoor air 
intake dampers open, the return air dampers close. The 
changeover from mechanical refrigeration to 
economizer operation is regulated by the standard 
single enthalpy input. To meet regulated air standards, 
the economizer control accepts an optional CO
2
 
input 
for
 
demand ventilation.With single enthalpy input, the 
economizer control monitors outdoor air. The dual 
enthalpy kit provides a second input used to monitor the 
return air. With a dual input kit installed, the economizer 
control compares the values of the two enthalpy or 
temperature inputs and positions the dampers to 
provide the maximum efficiency possible.
• Power Exhaust (Downflow only) - This accessory 
installs in the unit with a down flow economizer.
• Motorized Outdoor Air Damper - The motorized outdoor 
air damper includes a slide-in/plug-in damper assembly 
with an outdoor air hood and filters. The outdoor air 
dampers open to the preset position when the indoor fan 
motor is energized. The damper has a range of 0% to 
100% outdoor air entry. Factory installed option or field 
installed accessory.
• Alternate Indoor Blower Motor - For applications with 
high static restrictions, units are offered with optional 
indoor motors that provide higher static output and/or 
higher airflow, depending upon the installer’s needs.
• Variable Air Volume (VAV; 6-1/2 through 12-1/2 ton, 
only - A factory-installed variable frequency drive (VFD), 
mounted in the Blower Access compartment, is used to 
control the speed of the indoor blower motor in order to 
maintain a constant static pressure in the supply duct. A 
pressure transducer and VAV control board are mounted 
inside the control box. The drive comes completely wired 
and pre-programmed from the factory.
An optional, factory-installed manual bypass switch 
available with factory-installed VFD can be found in the 
Blower Motor Access compartment. The switch can be 
used to either route power to the VFD for modulating 
control of the blower motor, to bypass the drive and 
operate the motor at full speed, or to power the drive (and 
not the motor) for diagnostic purposes.
Due to space limitations, VAV is not available with any of 
the factory-installed BAS options, but is available with 
'BAS-ready' models. Terminal blocks are provided in the 
control box for field wiring of the customer-installed BAS.
A 'VFD-ready' option provides the provisions for a 
customer-installed drive. The unit comes with a mounting 
bracket installed in the Blower Access compartment which 
may accommodate other vendor's drives depending on 
their size. In order to utilize the unit's mounting bracket, 
the maximum recommended drive dimensions are limited 
to approximately 9" H x 5" W x 7.5" D.
If the drive will not fit in the allotted space, then it will have 
to be mounted elsewhere; either within the building on a 
perpendicular wall which is not subjected to excessive 
temperature, vibration, humidity, dust, corrosive gas, 
explosive gas, etc., or within an appropriate enclosure 
rated for outside installation to safeguard against 
moisture, dust and excessive heat. A terminal block 
located in the control box is provided for field connection 
of the VFD controls.
• Aluminized Steel Gas Heat Exchanger - For 
applications in non-corrosive environments. 
• Stainless Steel Gas Heat Exchanger - For applications 
in corrosive environments, this option provides a full 
stainless steel heat exchanger assembly.
• Stainless Steel Drain Pan - An optional rust-proof 
stainless steel drain pan is available to provide years of 
trouble-free operation in corrosive environments.
• Electric Heaters - The electric heaters range from 3kW to 
54kW and are available in all the voltage options of the 
base units. All heaters are intended for single point power 
supply.
• Disconnect Switch - For gas heat units and cooling units 
with electric heat, a HACR breaker sized to the unit is 
provided. For cooling only units, a switch sized to the 
largest electric heat available for the particular unit is 
provided. Factory installed option only.
• Convenience Outlet - (Non-Powered/Powered) - This 
option locates a 120V single-phase GFCI outlet with cover, 
on the corner of the unit housing adjacent to the 
compressors. The “Non-powered” option requires the 
installer to provide the 120V single-phase power source and 
wiring. The “Powered” option is powered by a stepdown 
transformer in the unit. Factory installed option only.
• Smoke Detectors - The smoke detectors stop operation 
of the unit by interrupting power to the control board if 
smoke is detected within the air compartment. Available 
for both the supply and/or return air configurations.
• Filters - 2” Pleated MERV 7 or 4” Pleated MERV 13 are 
available to meet LEED requirements. A 2” Throwaway is 
shipped as standard.