York TCGF24 Manuel D’Utilisation

Page de 22
413432-YTG-A-0608
20
Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the 
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCGF48S41S1
INDOOR COIL MODEL NO.
FC/MC/PC60
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1400
1600
1800
ID 
DB 
(°F)
80 80
75
80
80
80 80 75
80
80 80 80
75 80 80
ID 
WB 
(°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 
65
T.C.
44.1 45.2 43.0 47.2 47.3 44.2 45.3 43.9 47.4 47.9 44.2 45.3 44.8 47.6 48.5 
S.C.
43.7 39.0 33.0 31.2 24.2 44.3 40.6 34.5 32.2 24.8 44.9 42.3 36.0 33.2 25.5 
KW
2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.3 2.2 2.2 2.2 2.2 2.3 
75
T.C.
42.6 43.5 41.7 45.7 46.9 43.0 43.8 42.5 46.1 47.5 43.5 44.1 43.2 46.5 48.2 
S.C.
42.4 39.0 33.0 31.3 24.3 43.3 40.8 34.6 32.6 25.0 44.1 42.6 36.3 33.9 25.7 
KW
2.5 2.5 2.5 2.5 2.6 2.5 2.5 2.5 2.5 2.6 2.5 2.5 2.5 2.5 2.6 
85
T.C.
41.0 41.9 40.4 44.1 46.5 41.9 42.4 41.0 44.8 47.2 42.7 42.9 41.6 45.4 47.9 
S.C.
41.1 38.9 32.9 31.4 24.3 42.2 40.9 34.7 33.0 25.2 43.4 42.9 36.6 34.6 26.0 
KW
2.8 2.8 2.8 2.9 2.9 2.8 2.8 2.8 2.9 2.9 2.8 2.8 2.8 2.9 2.9 
95
T.C.
39.5 40.2 39.1 42.6 46.0 40.7 41.0 39.5 43.5 46.8 42.0 41.8 40.0 44.3 47.6 
S.C.
39.8 38.9 32.8 31.5 24.4 41.2 41.1 34.8 33.4 25.3 42.6 43.2 36.9 35.2 26.3 
KW
3.1 3.2 3.1 3.2 3.2 3.1 3.2 3.1 3.2 3.2 3.1 3.2 3.1 3.2 3.2 
105
T.C.
37.1 37.6 36.0 39.8 43.4 38.3 38.6 36.6 40.6 44.1 39.5 39.6 37.2 41.4 44.8 
S.C.
37.3 36.8 31.4 30.5 23.5 38.6 38.7 33.5 32.5 24.6 40.0 40.5 35.5 34.4 25.7 
KW
3.6 3.6 3.6 3.6 3.7 3.6 3.6 3.6 3.6 3.7 3.6 3.6 3.6 3.6 3.7 
115
T.C.
34.9 35.0 33.0 37.1 40.8 36.0 36.3 33.7 37.8 41.5 37.1 37.5 34.4 38.5 42.1 
S.C.
34.8 34.8 30.0 29.5 22.7 36.2 36.4 32.1 31.6 24.0 37.5 37.9 34.2 33.6 25.2 
KW
4.0 4.0 4.0 4.0 4.1 4.0 4.0 4.0 4.0 4.1 4.0 4.0 4.0 4.1 4.1 
125
T.C.
32.6 32.5 30.1 34.4 38.2 33.6 33.9 30.8 35.0 38.8 34.6 35.4 31.6 35.7 39.5 
S.C.
32.4 32.9 28.7 28.4 21.9 33.7 34.1 30.8 30.6 23.3 34.9 35.3 32.9 32.9 24.6 
KW
4.4 4.4 4.4 4.5 4.6 4.4 4.4 4.4 4.5 4.6 4.5 4.5 4.4 4.5 4.6 
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
-
FC/MC/PC48 
1.00 1.00 1.00 
-
FC/MC62 
1.01 1.00 1.00 
-
HD48 
1.00 1.00 1.00 
-
HD60 
1.02 1.02 1.00 
AHP/SHP60 
-
0.95 0.94 0.97 
AV/SV48 
-
0.95 0.94 0.96 
AV/SV60 
-
0.95 0.94 0.96 
F4FV060 
-
0.95 0.94 0.96 
F5FP048 
-
1.01 1.04 0.97 
F5FP060 
-
0.95 0.95 0.98 
MA16C 
FC/MC48C 
1.00 1.00 1.00 
MA20D 
FC/MC48D 
1.00 1.00 1.00 
MV16C 
FC/MC48C 
1.01 1.01 0.96 
MV20D 
FC/MC48D 
1.01 1.01 0.96 
MA16C 
FC/MC60C 
1.00 1.00 1.00 
MA20D 
FC/MC60D 
1.00 1.00 1.00 
MV20D 
FC/MC60D 
1.01 1.01 0.96 
MA20D 
FC/MC62D 
1.01 1.00 1.00 
MV20D 
FC/MC62D 
1.02 1.01 0.96 
Variable Speed 
Furnace
Coil
T.C.
S.C.
KW
PV8*C16
FC/MC/PC48C 
0.99 0.97 0.98 
PV8*C20
FC/MC/PC48C 
1.00 1.00 0.99 
P(C,V)9*C16
FC/MC/PC48C 
1.00 1.00 1.00 
P(C,V)9*C20
FC/MC/PC48C 
1.00 1.01 0.98 
PV8*C16
FC/MC/PC60C 
0.99 0.98 0.98 
PV8*C20
FC/MC/PC60C 
1.01 1.01 0.98 
P(C,V)9*C16
FC/MC/PC60C 
1.00 1.00 1.00 
P(C,V)9*C20
FC/MC/PC60C 
1.00 1.00 0.98 
P(C,V)9*D20
FC/MC/PC60D 
1.01 1.01 0.97 
PV8*C16
HD48 
0.99 0.97 0.98 
PV8*C20
HD48 
1.00 1.00 0.98 
P(C,V)9*C16
HD48 
1.00 1.00 1.00 
P(C,V)9*C20
HD48 
1.00 1.00 0.98 
P(C,V)9*D20
HD48 
1.01 1.00 0.97 
PV8*C16
HD60 
1.01 0.99 0.98 
PV8*C20
HD60 
1.02 1.02 0.98 
P(C,V)9*C16
HD60 
1.02 1.02 1.00 
P(C,V)9*C20
HD60 
1.02 1.02 0.98 
P(C,V)9*D20
HD60 
1.02 1.03 0.97 
PV8*C20
FC/MC62D 
1.01 1.01 0.98 
P(C,V)9*C16
FC/MC62D 
1.01 1.00 1.00 
P(C,V)9*C20
FC/MC62D 
1.01 1.01 0.98 
P(C,V)9*D20
FC/MC62D 
1.01 1.01 0.97