NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting
The following graphic is an example of a two-Module System (with four compressors). The setpoint is 
21.1°C (70°F) and the deadband is 2.2°C (4°F). Each compressor engages as the return air temperature 
reaches its assigned segment of the deadband above the setpoint. When the return air temperature drops 
back below the temperature assigned to a compressor, that compressor disengages. 
Caution: If the deadband setting is too narrow, it will cause the System to engage the 
compressors in response to a small temperature change. Since the compressors must run for a 
minimum period to avoid damage, this could over-cool the room. 
Caution: If the deadband setting is too wide, the System will not engage all of its cooling 
capacity until the return air temperature is significantly above the setpoint.
21
°
°
(70 ) 
Return air temperature
21.6
°
°
(71 ) 
22.2
°)
°
(72  
22.7
°)
°
(73  
23.3
°)
°
(74  
Compressor
# 1
  Compressor
# 2
  Compressor
# 3
  Compressor 
# 4
Cool Deadband Compressor Allocation 
Two-Module System