APC ACPCW40-150 Manuel D’Utilisation

Page de 92
InRoom Precision AC Tech Data Manual
42
Information common to both modes
PGE211
Cabinet Size 2
PGE311
Cabinet Size 3
PGE452
Cabinet Size 4
PGE612
Cabinet Size 5
Connection Sizes
Humidifier Supply Line - mm (in)
6 (1/4)
6 (1/4)
6 (1/4)
6 (1/4)
Condensate Drain Line - mm OD (in ID)
21 (3/4)
21 (3/4)
21 (3/4)
21 (3/4)
Fan Information 
Number  of  Fans
1
2
2
3
Air Flow - M³/hr (CFM)
6643 (3,910)
10007 (5,890)
14000 (8,240)
400 (14,130)
External Static Pressure - Pa (in WC)
50 (0.2)
50 (0.2)
50 (0.2)
50 (0.2)
Sound Power Level - dBA
71.2
71.9
76.7
79.5
Total Fan Power Consumption - kW (hp)
0.7 (0.9)
1.4 (1.9)
32.5 (3.4)
4.7 (6.3)
Humidification – Solid State Electrode, Canister
Flush Cycle
Automatic
Automatic
Automatic
Automatic
kg/hr (lb/hr)
8.0 (17.6)
8.0 (17.6)
15.0 (33.1)
15.0 (33.1)
Electric Reheat – Equally Loaded Three (3) phase 
Capacity - kW (BTU/hr) - Includes Motor Heat
460 V
12.0 (40982.4)
18 (61473.6)
18 (61473.6)
27 (92210.4)
230 V
9.0 (30736.8)
18 (61473.6)
18 (61473.6)
27 (92210.4)
Number  of  Stages
2
3
3
3
Downflow Filters - mm
Quantities
1050 x 453 x 47 G4
2
1
1
1
1050 x 398 x 47 G4
1
3
4
5
Upflow Filters - mm
Quantities
700 x 340 x 47 G4
1
N/A
1
1
700 x 332 x 47 G4
1
N/A
N/A
1
700 x 502 x 47 G4
1
1
1
1
700 x 508 x 47 G4
N/A
1
1
2
700 x 516 x 47 G4
N/A
1
N/A
N/A
Physical Data
Weight - kg (lb)
470 (1036)
584 (1287)
716 (1578)
893 (1969)
Height - mm (in)
1980 (77.95)
1980 (77.95)
1980 (77.95)
1980 (77.95)
Width - mm (in)
1000 (39.37)
1400 (55.11)
1750 (68.90)
2150 (84.65)
Depth - mm (in)
890 (35)
890 (35)
890 (35)
890 (35)