Honeywell L91B Manuel D’Utilisation

Page de 12
L91A,B,D PROPORTIONING PRESSURETROL
®
 CONTROLLERS
60-2152—08
2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or 
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
SPECIFICATIONS
L91A: Single potentiometer; nonadjustable proportioning 
range.
L91B: Single potentiometer; adjustable proportioning range.
L91D: Two potentiometers allow unison control of motors; 
adjustable proportioning range.
Electrical Rating: 24 Vac.
Potentiometer Action: Wiper moves toward W on pressure 
rise, toward B on pressure fall. Potentiometer is field 
replaceable.
Potentiometer Resistance: 140 ohms (nominal) for L91A, B, 
and D models.
Pressure Sensing Element: Brass bellows, 10-300 psi 
models phos-bronze bellows.
Minimum Ambient Temperature: 32° F (0° C)
Maximum Ambient Temperature: 150° F (66° C)
Adjustment Means: Screws on controller case top; knurled 
knob for main scale setting on 10 to 300 psi (0.07 to 2.07 
MPa) models.
Setpoint: At low pressure end of proportioning (throttling) 
range.
Main Scaleplate: Marked in both U.S. customary (oz/sq. in, 
psi, or in. Hg) and metric (kPa, MPa, or mm Hg) units.
Proportioning Range Scaleplate (L91B,D only): Gradu-
ated from A to F with a MIN (minimum) value below A. 
(See Table 2 for the value of each division.)
Mounting Means: Fitting on bellows has 1/4 - 18 NPT 
threads (external on 0 to 16 oz/sq. in., 0 to 4 psi, and 0 to 
15 psi models; internal on all other models) for mounting on 
a pipe or steam trap (siphon loop).
NOTE: Some models are available with 1/4 - 19 BSP-TR 
Also can be surface mounted by screws through two knockout 
holes in case back.
Table 1. Models available.
Operating Ranges
a
Proportioning (Throttling) Range at Midscale
Maximum Surge 
Pressure
Model
U. S. 
Customary 
Units
Metric Units
Potentiometer 
Part No.
b
Adjustable
U. S. 
Customary 
Units
Metric Units
psi
kPa
L91A 0 to 15 psi
0 to 103 kPa
23176CB
No
0.5 psi
3.4 kPa 25
172
5 to 150 psi
0.03 to 1.03 MPa 23176CB
No
5 psi
0.03 MPa
225
1551
10 to 300 psi
b
0.07 to 2.07 MPa 23176CB
No
12 psi
0.08 MPa
350
2413
L91B 0 to 15 psi
0 to 103 kPa
23176CF
Yes
1.5 to 12 psi
10 to 83 kPa
25
172
5 to 150 psi
c
0.03 to 1.03 MPa 23176CB
Yes
5 to 23 psi
35 to 160 kPa
225
1551
10 to 300 psi
c
0.07 to 2.07 MPa 23176CB
Yes
12 to 48 psi
85 to 330 kPa
350
2413
10 to 300 psi
0.07 to 2.07 MPa 23176CF
Yes
30 to 110 psi
0.21 to 0.76 MPa 350
2413
L91D 0 to 15 psi
0 to 103 kPa
23176CF
Yes
1.5 to 12 psi
10 to 83 kPa
25
172
5 to 150 psi
c
0.03 to 1.03 MPa 23176CF
Yes
13 to 52 psi
0.09 to 0.36 MPa 225
1551
10 to 300 psi
c
0.07 to 2.07 MPa 23176CF
Yes
30 to 110 psi
0.21 to 0.76 MPa 350
2413