Monessen Hearth CSDV20DLP Manuel D’Utilisation

Page de 44
14
58D6056
CSDV Series Direct Vent Gas Stove
Outside Corner
Inside Corner
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors. 
G =
Combustible 
  6" (152 mm)
Noncombustible 
  2" (51 mm)
F =
Combustible 
  6" (152 mm)
 
Noncombustible 
  2" (51 mm)
G
Balcony - 
with no side wall
M = 
Combustible &
Noncombustible
  12" (305 mm)
M
Balcony - 
with perpendicular side wall
M = 24" (610 mm)
P = 20” (508 mm)
M
F
Alcove Applications*
C
D
C
E
V
V
Combustible &
Noncombustible
V
V
V
E
 = Min. 6” (152 mm) for 
non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls
O
 = 8’ (2.4 m) Min.
O
P
Figure 12 - 
Allowable 
Venting 
584-15
 
No. 
  of Caps 
 
D
Min.
 
  C
Max.
 
3’ (914 mm)  2 x D
Actual
 
6’ (1.8 m) 
1 x D
Actual
 
9’ (2.7 m) 
2/3 x D
Actual
 
12’ (3.7 m) 
1/2 x D
Actual
D
Min.
 = # of Termination caps x 3
C
Max.
 = (2 / # termination caps) x D
Actual
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or 
non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All mechanical air intakes within 10’ (1 m) of a 
termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must 
be a minimum of 1’ (305 mm) below the termination cap.
VENTING INSTALLATION 
  2
  0
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
HORIZONTAL RUN 20' MAX (6.1m)
VER
TICAL
 HEIGHT
 40' MAX (12.2m)
(MEASURED FROM ST
OVE 
T
OP) 
NOTE: Any vent configurations within
the shaded areas are acceptable.
Use Restrictor
Disk Above 
Dotted
Line 
Minimum Height from Stove Top 18" 
ST1136
venting graph
Actual Stove Height
CSDV20 = 23Z\x" (597 mm)
CSDV30 = 28Z\x" (724 mm)
CSDV40 = 30Z\x" (775 mm)
minimum Height from
Stove Top
CSDV20 = 18" (457 mm)
CSDV30 = 30" (762 mm)
CSDV40 = 30" (762 mm)
Figure 13 - 
Acceptable Venting 
Configurations