Quadra-Fire CB1200-B Manuel D’Utilisation

Page de 48
Page  14
7014-082D
September 1, 2008
CB 1200 Pellet Stove 
We  recommend  a  minimum  of  60  in. 
(1524mm) vertical, however above the eave 
is preferred. 
Both  installations  are  approved  for  mobile 
home installations.  Must use  or 4 inch (76 
to 102mm) “L” or “PL” Listed pellet venting or 
listed double wall pipe and Quadra-Fire out-
side  air kit  in mobile homes.  Single wall pipe 
is approved for residential installations only.
C.  Vertical
D. Through The Wall & Vertical
Firestop
Flashing
Rain Cap
6 in.
(152mm)
Min.
Non-combustible Hearth Pad
 in. (76mm)
Min.
Clean-out
Cover
24 in. (610mm)
minimum
Ceiling Support
Class A Chimney
Connector Adapter
Top Vent Kit
Non-Combustible Hearth Pad
Clean-out Cover
Tee
Wall Thimble
Support Bracket
every 60 in. (1524mm)
24 in. (610mm)
Minimum
Rain Cap
Flashing
2 in. (51mm) Minimum
6 in. (152mm)
Minimum
Figure 14.1
Figure 14.2