Enviro 1200 Freestanding Manuel D’Utilisation

Page de 45
Installation
Hearthpad
Floor
Pedestal
Woodstove
Optional
fan
Outside air connection
through wall or floor
Chimney
connector
Ceiling
Insulated chimney
Roof flashing
Roof
Roof radiation
shield (if required)
Minimum air space
in accordance with
chimney manufacturer.
Wall support
Chase
(optional)
Insulated corner
Minimum
18" (475 mm)
Rain cap/
Spark arrestor cap
Storm Collar
ridge,  the  chimney  must  be  2 
feet (60.9 cm) above the ridge. 
Refer to Figure 22.
Note:  Increasing  the  chimney 
height  above  the  roof  may 
help  your  unit  to  draft  better. 
This greater draft can decrease 
problems  such  as  difficult 
start-ups,  smoke  coming  out 
when  door  is  open,  and  dirty 
glass.  You  may  initially  try 
the  minimum  required  height 
and  if  problems  do  arise,  add 
additional height later.
10. Slide the roof flashing over your 
chimney  and  seal  the  flashing 
to  the  roof  with  a  roofing 
compound.  Secure  the  roof 
flashing  to  your  roof  with  nails 
or screws.
11. Place the storm collar over the 
flashing and seal the joints with 
silicone caulking.
12. Fasten  the  rain  cap  /  spark 
arrestor cap to the top of your 
chimney.
13. Place  the  stove  back  into 
position.
14. Install  the  chimney  connector 
Figure 24: Standard Horizontal Installation.
pipe with the lower (crimped) edge of the pipe inside the flue collar. Any creosote formed will then run 
back down into the stove. All connections must be tight and secured with three sheet metal screws 
equally spaced. Double wall pipe is recommended over single wall.
15. Also install an outside air flex pipe to the stove.
IMPORTANT: When a metal prefabricated chimney is used, the manufacturer’s installation instructions 
must be followed. You must also purchase and install the ceiling support package or wall pass-through 
and “T” section package, firestops (where needed), insulation shield, roof flashing, chimney cap, etc. 
Maintain proper clearance to the structure as recommended by the manufacturer. The chimney must be 
the required height above the roof or other obstructions for safety and proper draft operation.
Note: If you are using a horizontal connector (refer to Figure 24), the chimney connector 
should  be  as  high  as  possible  while  still  maintaining  the  18”  (475  mm)  minimum 
distance from the horizontal connector to the ceiling.