Lightolier 26050 Fascicule

Page de 2
FALL RIVER, MASSACHUSETTS 02720
MONTREAL, QUEBEC, CANADA
 © 1997
INSTRUCTION SHEET NO.
A0197
Page 1 of 2
IS:26050
Installation Instructions for ProSpec, In-Line, "L", "T", and "X" Connectors / Circuit Diagrams
For use with ProSpec
 Track System Only.
Caution:
• Turn off power at fuse box before installing  track.
• Instructions for grounding Feed-in Kit must be followed.
Failure to do so may result in a hazardous condition.
• Use only #12 ga. solid copper wire in connectors to
maintain proper track rating.
• Observe polarity, white (neutral) wire must be connected
to terminal marked "NEUT". Failure to observe Polarity may
result in an electrical hazard.
• Do not use Track as a conduit support. Independent conduit
supports (such as suitable conduit straps) must be used to
attach the conduit installation to the building structure.
INSTALLING CONNECTOR INTO TRACK SECTION
1. Remove Dead-End Cover if necessary by pulling it out of track
(save Dead-End Cover).
2. Push Connector into the track until there is no gap between the
track unit and connector. Ensure that the contact blades are
aligned with the copper wires in the track during assembly.
3. Tighten the locking screw(s).
POWER FEED TO THE CONNECTOR(S)
DIRECT POWER FEED
1. Remove the bottom cover (if required) by snapping it out of the
connector (save cover).
2. Remove K.O. plate from the connector.
3. Remove the K.O..
4. Attach the electrical connector onto the K.O. plate using the nut
provided. Align the electrical connector such that the connector is
hidden by the track width.
5. Attach the K.O. plate onto the connector using the screw that was
previously removed.
6. Pass cable or conduit through electrical connector and clamp cable
or conduit to electrical connector.
7. Form the wires to the appropriate screw terminals, cut and strip
wires and attach to the screw terminals (see wiring section of
instruction sheet).
8. Snap the bottom cover onto the connector.
There are additional feed in kits (Floating Canopy, End Feed Canopy,
Floating Invisible Feed, Grid Ceiling Canopy Kit, Stem Kits....) that can
be used with these connectors. See the Instruction Sheet supplied
with the Feed-in Kit for detailed instructions on mounting the kit to
the connector.
READ AND UNDERSTAND ALL TRACK, CONNECTOR, FEED-IN-KITS, AND ACCESSORY
INSTRUCTION SHEETS BEFORE INSTALLING ANY PROSPEC™ TRACK ITEM.
This fixture is intended for installation in accordance with the National Electrical Code and local or Federal
code specifications. To assure full compliance with codes and regulations, check with your local electrical
inspector before installation. To prevent electric shock, turn off electricity at fuse box before proceeding.
Retain these instructions for maintenance reference.
Fig. 3
Connector
Track Unit
Connector
Track Unit
Locking Screw
Bottom Cover
Fig. 1
Track Unit
Dead End
Fig. 2
Dead End
Bottom Cover
Electrical Connector
(by Others)
K.O. Plate
Nut
Track Unit
Knock Out