Lightolier FBPPL Fascicule

Page de 1
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • B0308
Job Information 
Type:
Job Name: 
Cat. No.: 
Lamp(s): 
Notes:
 
FBP Series Fluorescent Emergency Ballast
 
FBPPL
Page 1 of 1 
One Lamp Operation 825 Lumens
Lightolier is a Philips group brand
Lead Calcium Battery
The FBP Series quickly converts standard fluorescent luminaires into emergency luminaires.
11.3”
(28.7 cm)
10.6”
(26.9 cm)
3.6”
(9.1 cm)
2.3”
(5.8 cm)
Features
1.  Lamp Operation: Operates the following lamp types: T4 Compact fluores-
cent (2 pin with integral starter). See Lamp Operation and performance table 
for specific lamp performance and operation.
2.  Illumination: Provides 90 minutes of emergency illumination, and produces 
a maximum of 825 lumens initial emergency light output. .
3.  Housing: Constructed of 20 gauge galvanized steel. Housing allows for hous-
ing frame mounting on most recessed luminaires.
4.  Electronics: 120/277 VAC dual voltage input with surge-protected, solid-
state circuitry. Charging system is complete with AC indicator lamp and test 
switch.
5.  Battery: Maintenance free, sealed lead calcium battery has an estimated 
service life of 5 years, and an operating temperature range of 20°F (7°C) to 
95°F (35°C).
6.  Input Power Requirements: 3.5 watts max.
7.  Warranty: Electronics: 2 years; Battery: 2 years.
Code Compliance
UL 924 listed.
Options
ST = Special Input Transformer for 220 VAC/50 Hz, 240 VAC/50Hz. Contact fac-
tory for other input voltages and frequencies. 
Accessories
CCAPS = Wire bundle cover for mounting external to luminaire
Complete Fixture consists of ballast unit. Select options and accessories below.
Model # 
Max. Lumens 
Lamp Operation 
 
FBPPL 
825 
One
Lamp Operation and Performance
   
 
 
   Emerg. Op. 
  
 
     
 
Non-Emerg. 
Max. 
Max. 
Emer 
 Lamp 
 
Base 
 Lumen 
Lumen 
Lamp
 Type  Watt.  
Type 
Output 
Output 
Operation
 F5BXT4 
G23/2 Pin 
250 
250 
One Only
 F7BXT4 
G23/2 Pin 
400 
400 
One Only
 F9BXT4 
G23/2 Pin 
600 
600 
One Only
 F13BXT4  13 
GX23/2 Pin 
825 
825 
One Only
Notes: 
1.  Maximum non-emergency lumen output can vary based on lamp manufacturer, ambient operating 
temperature, and ballast manufacturer.
2.  Maximum emergency lumen output is based on total output of one or two lamps, and can vary 
based on lamp manufacturer and ambient operating temperature.
3.  Maximum emergency lumen output is supported for a full 90 minutes of operation.
4.  Consult factory for compatibility, operation and performance of lamp types not listed.