Ei144 DataSht RevA
 
 
Model 
Ei144 Heat 
 
Easi-Fit base 
 
9V Alkaline Battery back up 
 
Fixed temperature fast response thermistor type 
sensor, range 54°C to 62°C 
 
Test/Hush button 
 
Advanced suppression and calibration technology 
 
Interconnectable to other Ei mains powered alarms 
 
Low power cell warning 
 
Kitemarked to BS5446-2:2003 
 
5 year guarantee 
 
 
Product Description 
 
The Ei144 is a Heat Alarm that runs on 230V AC mains 
power, and has a 9V alkaline battery back up in the 
event of mains failure. The 9V battery will last for up to 4 
years in standby mode, and capable of powering the 
heat detector for up to 2 years in the event of mains 
failure. 
 
The Ei144 is supplied with the Easi-Fit base that allows 
very quick and simple installation of the heat alarm. The 
Easi-Fit base automatically connects both mains power 
and battery as the detector head slides on to the Easi-Fit 
base. 
 
The Ei144 has the ability to interconnect up to twelve 
alarms to allow all alarms to sound if just one of the 
interconnected alarms should be triggered. 
 
The Ei144 has built in circuitry to aid suppression of 
voltage transients and RF interference to further reduce 
the chances of false alarms under such conditions. 
 
The Ei144 heat alarm gives a fire warning when the 
temperature at the unit reaches 58
0
C. Heat alarms are 
ideal for use in kitchens and garages, where the use of 
optical or ionisation alarms would lead to unwanted 
nuisance alarms. 
 
On escape routes this alarm must be interconnected 
with smoke alarms.
 
 
Operation 
 
 
The green indicator will illuminate to show mains 
power is present 
 
 
The red indicator will flash every 40 seconds to 
show that the detector has performed an automatic 
self test 
 
 
The red indicator will flash rapidly to show an alarm 
condition for the heat detector 
 
 
The “Test/Hush” button will either silence false 
alarms or perform a unit self test 
 
 
In “Test” mode the alarm will perform a self test and 
sound the horn  
 
 
In “Hush” mode the alarm enters a ten minute period 
of reduced sensitivity to overcome false alarm 
conditions, and will then automatically reset itself 
 
 
When interconnected to other Ei mains powered 
alarms, an alarm on one detector will trigger all other 
interconnected alarms within one second (only the 
triggered alarm will flash a red indicator) 
 
 
The heat detector will emit a beep every 40 seconds 
to indicate that the battery back up is depleted and 
needs replacing
 
 
 
 
MAINS POWERED 230V~ 
9V Alkaline Battery Back-Up