Chapter 8 Network variable bindings
126
BAS-APG001-EN
UUKL binding list (smoke alarm status)
Table 32 shows an example list of smoke alarm custom bindings. In order 
to comply with UL-864 annunciation and control requirements, smoke 
alarm signals are sent to the mechanical system, FSCP lamps, and audio 
alarms (Sonalerts). Smoke alarms specific to a zone are broadcast to 
annunciate smoke alarms regardless of control sequence. A general 
smoke alarm is broadcast to signal a switch from HVAC control mode to a 
smoke control mode. Floor alarms are sent as an analog value to comply 
with the subsequent alarms requirement.
Table 32.  Smoke alarm custom bindings
Function
Originator
Network variable
Destination
Smoke alarm any
 MP580-2
nvoSwitch02
Mechanical system /nviSwitch37
nvoSwitch02
MP580-3/nviSwitch37
nvoSwitch02
MP580-4/nviSwitch37
smokeAlarmFloor01
MP580-2
nvoSwitch05
Mechanical system /nviSwitch20
nvoSwitch05
MP580-3/nviSwitch09
smokeAlarmFloor02
 MP580-2
nvoSwitch06
Mechanical system/nviSwitch21
nvoSwitch06
MP580-3/nviSwitch12
smokeAlarmFloor03
MP580-2
nvoSwitch07
Mechanical system/nviSwitch22
nvoSwitch07
MP580-4/nviSwitch08
smokeAlarmFloor04
MP580-2
nvoSwitch08
Mechanical system/nviSwitch23
nvoSwitch08
MP580-4/nviSwitch11
supplyDuctSmokeDetect
MP580-2
nvoSwitch09
Mechanical system/nviSwitch30
nvoSwitch09
MP580-3/nviSwitch06
returnDuctSmokeDetect
MP580-2
nvoSwitch10
Mechanical system/nviSwitch31
nvoSwitch10
MP580-4/nviSwitch05
stairDuctSmokeDetect
 MP580-2
nvoSwitch11
Mechanical system/nviSwitch32
nvoSwitch11
MP580-4/nviSwitch01
stairShaftSmokeDetect
MP580-2
nvoSwitch12
Mechanical system/nviSwitch33
smokeFloorAlarm
MP580-2
nvoPercent20
Mechanical system/nviPercent20
nvoPercent20
MP580-3/nviPercent20
nvoPercent20
MP580-4/nviPercent20