System Sensor 2112 Manuel D’Utilisation

Page de 4
D200-61-00                                                                                               1                                                                                                I56-930-02
2112/24TSRB Photoelectronic 
Smoke Detector
INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS
A Division of Pittway
 3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Before Installing 
Please  thoroughly  read  System  Sensor  manual  I56-407, 
Guide  for  Proper  Use  of  System  Smoke  Detectors,  which 
provides  detailed  information  on  detector  spacing,  place-
ment,  zoning,  wiring,  and  special  applications.  Copies  of 
this manual are available at no charge from System Sensor.
NOTICE: This manual should be left with the owner/user 
of this equipment.
IMPORTANT: This detector must be tested and maintained 
following  NFPA  72  requirements.  The  detector  should  be 
cleaned at least once a year.
General Description
The Model 2112/24TSRB is a 4-wire photoelectronic smoke 
detector that uses a state-of-the-art optical sensing cham-
ber.  This  detector  is  designed  to  provide  open  area  pro-
tection. It features a restorable, built-in, fixed-temperature 
(135°F) thermal sensor.
Installation of this detector is simplified by the use of the 
Specifications
Diameter:                                               5.5 inches (140 mm)
Height (including mounting bracket):      1.7 inches (43 mm)
Weight:                                                  5.3 oz. (150 g)
Operating Temperature Range:                32° to 100°F (0° to 39°C)
Operating Humidity Range:                     10% to 93% relative rumidity, noncondensing
Latching Alarm:                                     Reset by momentary power interruption
Heat Sensor:                                          135°F fixed temperature electronic thermistor
Electrical Ratings
System Voltage                                       nominal: 
12 or 24 VDC
                                                             Minimum: 
8.5 VDC
                                                             Maximum: 
35 VDC
Maximum Ripple Voltage:                       30% of nom. voltage (peak to peak)
Standby Current:                                    15 mA maximum
Alarm Current:                                      
                                                             at 12V:  38 mA maximum
                                                             at 24V:  
45 mA maximum
Reset Voltage:                                         0.8 VDC minimum
Reset Time:                                            0.3 seconds maximum
Start-up Time:                                        30 seconds maximum (after 30 second reset)
Supervision and Alarm Initiation Contact Ratings
Resistive or inductive load (60% power factor)
Form A:                                                 0.5A @ 30 VAC/DC 
mounting  bracket  and  plug-in  screw  terminal  block  that 
can  be  prewired  to  the  system,  allowing  the  detector  to 
be easily installed or removed for cleaning. The detector’s 
sensitivity can be tested in place using the MOD400R Test 
Module (available separately from System Sensor).
The 2112/24TSRB features a supervisory relay that super-
vises the power and the sensitivity of the detector. When 
the  power  to  the  detector  is  lost,  the  supervisory  relay 
opens instantaneously. Where as, when the detector devi-
ates from its sensitivity range indicating the need for main-
tenance,  the  supervisory  relay  opens  after  a  maintenance 
condition has continuously existed for 30 to 35 minutes.
An LED on the detector provides a local visual indication 
of the detector’s status. If power is applied to the detector, 
and it is functioning normally in standby, the status LED 
blinks every ten seconds.  The LED latches on in alarm and 
quits flashing when the detector deviates from its sensitiv-
ity range.