Greenheck Fan No Flow Duct Smoke Detector Manuel D’Utilisation

Page de 4
NO FLOW DUCT 
SMOKE DETECTOR
Purpose/Application
National and local safety standards and codes recognize the 
ability of air duct systems to transfer smoke, toxic gases, and 
flame from area to area. Sometimes smoke can be of such 
quantity as to be a serious hazard to life safety unless blowers 
are shut down and dampers are actuated. The primary purpose 
of duct smoke detection is to prevent injury, panic, and property 
damage by reducing the spread (recirculation) of smoke. The 
detector samples air currents passing through a duct and 
gives dependable performance for management of smoke and 
combination fire smoke dampers. Duct smoke detection can 
also serve to protect the air conditioning system itself from fire 
and smoke damage. 
There are several important documents that provide guidance 
concerning the performance, application and installation of duct 
detectors: 
 
1) NFPA Standard 90A, Installation of Air Conditioning 
 
     and Ventilation Systems
 
2) NFPA Standard 92A, Recommended Practice for 
                 Smoke Control Systems
 
3) NFPA Standard 72, National Fire Alarm Code
 
4) NFPA Standard 101, Life Safety Code
 
5) UL Standard 268A, Standard for Smoke Detectors for 
                 Duct Applications
 
6) ASHRAE Handbook and Product Directory, “Fire and 
                 Smoke Control”
 
7) System Sensor, Guide for Proper Use of Smoke 
                 Detectors in Duct Applications.
Duct detectors are:
        NOT a substitute for an open area smoke detector
        NOT a substitute for early warning detection
        NOT a replacement for a building’s regular fire detection 
        system
Specifications
 
 
 
  
Type:  Photoelectric
       
         Air Duct Velocity:   0 to 3000 fpm (0 to 15.2 m/s)
Operating Temperature Range:  32°F to 120°F (0° to 49°C)
       Operating Humidty Range:  10% to 93% RH
 
       Operation Voltage:  120 VAC
Features
•  Designed for mounting on standard electrical box
•  Low-profile smoke detector design
•  Field adjustable sensitivity
•  Built-in test switch
Listings
UL 268A
Refer to Greenheck Installation Supplement: Part # 465915- No 
flow smoke detector IOM
#10 TEK SCREW
4 X 4 X 2 1/8 HANDI BOX
SMOKE DETECTOR ASSEMBLY