Special environmental conditions 
 
When using the VCB in special environments, check the points in Table 1 below. 
 
Table 1 Points to Check When Using the Circuit Breaker in Special Environments 
 
Special  
environmental 
condition 
Practical example 
Check points 
Contamination 
* Large amounts of dust. 
 
* Salt corrosion (locations near the 
seashore or where winds containing 
salts blow) 
 
* Reduce the size of the ventilation duct 
 
* Make sure the wind does not blow 
directly at the location where the 
ventilation duct is installed 
 
* Install a filter 
 
High humidity 
* Places subject to frequent and/or 
strong rainstorms or snowstorms 
 
* When there is a cooling tower or 
other large water source nearby 
 
* Where there is condensation (which 
forms when the humidity in the 
cubicle drops dramatically) 
* Use a cubicle construction that will 
prevent condensation from forming 
 
* Use a cubicle construction that will 
prevent the wind from blowing directly 
into the cubicle 
 
* Install a space heater 
 
Corrosive gases 
* When corrosive gases are produced 
at plants handling raw materials, at 
water treatment plants, in hot 
springs regions etc. (hydrogen 
chloride, sulfurous acid, nitrogen 
oxide, ammonia, chlorine, ozone 
etc. or other gases) 
 
* Use a cubicle construction that 
enables the cubicle to be blocked off 
from the outside air to the greatest 
extent possible 
 
* Install a filter