Micro Motion
®
 Series 3000 MVD Transmitters and Controllers
Specifications – Model 3350 and Model 3700
Discrete outputs
Three discrete outputs
Configurable for the application
Polarity: Active high or active low, software selectable
Power: Internal pull-up to 24 V
Voltage: 24 VDC nominal
Current: Sourcing at 5.6 mA when V
out
 = 3 VCD; sinking up to 500 mA at 30 VDC maximum
Frequency/pulse output
One 2-wire frequency/pulse output
Output is linear with flow rate to 12,500 Hz
Configurable unit of measure
Scalable to 10000 Hz
Pulse width: 50% duty cycle above 500 Hz, configurable for frequencies below 500 Hz
Power: Active or passive, software selectable
Polarity: Active high or active low, software selectable
Voltage: 24 VDC nominal, active; 30 VDC applied maximum, passive
Current: Sourcing, 10 mA at 3 VDC, active; sinking, 500 mA, active or passive
Fault output
When a fault is detected, outputs go to configured states. User can select high, low, last measured 
value, or internal zero. Milliamp outputs conform to NAMUR NE43 (June 1994).
High output limits can be configured from 21 to 24 mA for milliamp; 15,000 Hz for frequency
Low output limits can be configured from 1 to 3.6 mA for milliamp; 0 Hz for frequency
Last measured value is the last output for the process variable
Internal zero drives the milliamp and frequency outputs for process variables to zero values
B.6.4
Digital communications
One RS-485 port (standard)
-
Supports Modbus RTU, Modbus ASCII, HART/RS-485, or printer
-
User-configurable
HART superimposed on primary mA output
-
Standard HART/Bell 202 communication parameters, not configurable
External adapters (not included) required for conversion to RS-232