5. Add resistance as required. 
For HART/Bell 202 connections, the signal converter must be connected across a 
resistance of 250–600
Ω. See the ProLink II manual for more information.
For RS-485 connections, additional resistance may or may not be required. See the 
ProLink II manual for more information.
6. Start ProLink II and click 
Connection > Connect to Device
. In the Connect dialog box:
a.
Select the protocol for your connection type. The ProLink II dialog box is updated to 
reflect your choice.
b.
Set other required parameters.
c.
Click 
Connect
.
7. If you are using an RS-485 connection, the RS-485 terminals may not be in the desired mode. 
To change mode:
a.
Power-cycle the device.
b.
To connect in service port mode, click 
Connect
 within the 10-second interval after 
power-up.
c.
To connect in RS-485 mode, wait more than 10 seconds, then click 
Connect
.
G.5
ProLink II menu flowcharts
This section contains flowcharts for the ProLink II main menu and the configuration menu. These 
flowcharts are based on:
ProLink II v2.6
Series 3000 device software rev7.0