Emerson Series 3000 MVD Manuel D’Utilisation

Page de 348
Configuration and Use Manual
69
Configuring Outputs
Con
fig
ur
in
g Batch
C
o
n
fi
gu
ri
ng
 Pr
oce
ss Mon
ito
r
Con
fig
ur
in
g Ou
tpu
ts
Con
fig
ur
in
g Eve
n
ts
Note: Beginning with rev7.0 of the transmitter software, if the LRV and URV are changed from the 
defaults, and the milliamp output source is later changed, the LRV and URV will not be reset to their 
default values. For example, if mass flow is assigned to the milliamp output, and the LRV and URV 
for mass flow are changed, then density is assigned to the milliamp output, and finally mass flow is 
reassigned to the milliamp output, the LRV and URV for mass flow are reset to the configured values. 
In earlier versions of the transmitter software, the LRV and URV were reset to factory default values.
Multiple cutoffs
Cutoffs can be configured for the mA output and also for the mass flow and volume flow process 
variables. If mass flow or volume flow has been assigned to an mA output, a non-zero value is 
configured for the flow cutoff (see Section 7.3), and the mA output’s Low Flow Cutoff is also 
configured, the cutoff occurs at the highest setting, as shown in the following examples.
See Section 7.3 for information on the mass flow, volume flow, and density cutoffs.
Multiple damping parameters
Damping can be configured for the mA output and also for the mass flow, volume flow, density, and 
temperature process variables. If damping has been configured for the process variable assigned to an 
mA output (see Section 7.3), and a non-zero value is configured for Damping Seconds for the same 
mA output, the effect of damping the process variable is calculated first, and the Damping Seconds 
calculation is applied to the result of that calculation. See the following example.
Example
Configuration:
Primary mA output: Mass flow
Frequency output: Mass flow
AO cutoff for primary mA output: 10 g/sec 
Mass flow cutoff: 15 g/sec
As a result, if the mass flow rate drops below 15 g/sec, all outputs 
representing mass flow will report zero flow.
Example
Configuration:
Primary mA output: Mass flow
Frequency output: Mass flow
AO cutoff for primary mA output: 15 g/sec 
Mass flow cutoff: 10 g/sec
As a result:
If the mass flow rate drops below 15 g/sec but not below 10 g/sec:
-
The primary mA output will report zero flow.
-
The frequency output will report nonzero flow.
If the mass flow rate drops below 10 g/sec, both outputs will report 
zero flow.