Emerson Series 3000 Manuel D’Utilisation

Page de 28
Micro Motion
®
 Series 3000 Transmitters and Discrete Controllers
7
Output signals 
continued
 
Fault indication
When a fault is detected, outputs go to configured states. User can select upscale, downscale, internal zero, or none. Milliamp 
outputs conform to NAMUR NE43 (June 1994).
Upscale
Milliamp
21 to 24 mA, user configurable
Frequency
15,000 Hz
Downscale
Milliamp
1 to 3.6 mA, user configurable
Frequency
0 Hz
Internal zero
Drives the mA and frequency outputs for process variables to zero values
None
Ignores fault conditions
Digital communications
RS-485 port
One pair of terminals supports SP (service port) mode or RS-485 mode. On device power-up, the 
user has 10 seconds to connect in SP mode. After 10 seconds, the terminals switch to RS-485 
mode. The communication parameters in SP mode are:
Data rate
38,400 baud
Parity
No parity
Stop bit
One stop bit
Address
111
In RS-485 mode, the Series 3000 can communicate via Modbus RTU, Modbus ASCII, or HART
(1)
 
protocols. The communication parameters are configurable with ProLink II software, Modbus, or 
the display. The shipped default parameters are:
(1) Using HART, it is possible to configure basic transmitter functionality, and read/write batch setpoints and totals. Series 3000 batch 
applications or enhanced density applications cannot be configured using HART. Using Modbus, all transmitter functionality, batch 
commands, and batch applications can be controlled.
Data rate
9600 baud
Parity
Odd
Stop bit
One stop bit
The RS-485 port can also be configured as a printer port (see below).
HART Bell 202
The HART Bell 202 signal is superimposed on the primary mA output, and is available for host 
system interface. The HART Bell 202 communication parameters are:
Frequency
1.2 and 2.2 KHz
Amplitude
0.8 mA peak-to-peak
Data rate
1200 baud
Resistance
Loop requires 250 to 600 Ohms resistance
Printer port
The RS-485 port can be configured as a printer port. When the RS-485 port is 
configured as a printer port, it cannot be used for any other function.
Requires external RS-232 adapter (not included)
Bidirectional with Epson printer; send only with all other printers and when using a multidrop 
configuration