If you use ProLink II or ProLink III to set HART Address to 
0
, the program automatically enables
Loop Current Mode
. If you use ProLink II or ProLink III to set HART Address to any other value, the
program automatically disables Loop Current Mode. This is designed to make it easier to
configure the transmitter for legacy behavior. Always verify Loop Current Mode after setting
HART Address
.
3.
(Optional) Enable and configure Burst Parameters.
Tip
In typical installations, burst mode is disabled. Enable burst mode only if another device on
the network requires burst mode communication.
4.
(Optional) Configure HART Variables.
Configure burst parameters
Display
Not available
ProLink II
ProLink
 > Configuration > Device > Burst Setup
Field Communicator Configure > Manual Setup > Inputs/Outputs > Communications > HART Burst Mode
Overview
Burst mode is a mode of communication during which the transmitter regularly
broadcasts HART digital information over the primary mA output. The burst parameters
control the information that is broadcast when burst mode is enabled.
Tip
In typical installations, burst mode is disabled. Enable burst mode only if another device on the
network requires burst mode communication.
Procedure
1.
Enable Burst Mode.
2.
Set Burst Mode Output as desired.
Label
Description
ProLink II
ProLink III
Field Communi-
cator
Primary Variable
Source (Primary
Variable)
PV
The transmitter sends the primary
variable (PV) in the configured
measurement units in each burst
(e.g., 14.0 g/sec, 13.5 g/sec,
12.0 g/sec).