(Optional) Set Additional Communications Response Delay in “delay units.”
A delay unit is 2/3 of the time required to transmit one character, as calculated for
the port currently in use and the character transmission parameters. Valid values
range from 1 to 255.
Additional Communications Response Delay
 is used to synchronize Modbus
communications with hosts that operate at a slower speed than the transmitter. The
value specified here will be added to each response the transmitter sends to the
host.
Tip
Do not set Additional Communications Response Delay unless required by your Modbus host.
6.7.4
Configure Digital Communications Fault Action
Display
Not available
ProLink II
ProLink
 > Configuration > Device > Digital Comm Settings > Digital Comm Fault Setting
Field Communicator Configure > Alert Setup > Inputs/Outputs Fault Actions > Digital Communications
Overview
Digital Communications Fault Action
 specifies the values that will be reported via digital
communications if the transmitter encounters an internal fault condition.
Procedure
Set Digital Communications Fault Action as desired.
The default setting is None.
Options for Digital Communications Fault Action
Options for Digital Communications Fault Action
Table 6-17:   
Label
Description
ProLink II
ProLink III
Field Communicator
Upscale
Upscale
Upscale
Process variable values indicate that the
value is greater than the upper sensor lim-
it.
Totalizers stop incrementing.
Downscale
Downscale
Downscale
Process variable values indicate that the
value is greater than the upper sensor lim-
it.
Totalizers stop incrementing.