Emerson 9739 Manuel D’Utilisation

Page de 256
4.4.1
Options for Flow Direction
Options for Flow Direction
Table 4-4:   
Flow Direction
 setting
Relationship to Flow Direction ar-
row on sensor
ProLink II
ProLink III
Field Communicator
Forward
Forward
Forward
Appropriate when the Flow Direction
arrow is in the same direction as the
majority of flow.
Reverse
Reverse
Reverse
Appropriate when the Flow Direction
arrow is in the same direction as the
majority of flow.
Absolute Value
Absolute Value
Absolute Value
Flow Direction arrow is not relevant.
Bidirectional
Bidirectional
Bi directional
Appropriate when both forward and
reverse flow are expected, and for-
ward flow will dominate, but the
amount of reverse flow will be signifi-
cant.
Negate Forward
Negate Forward
Negate/Forward Only
Appropriate when the Flow Direction
arrow is in the opposite direction from
the majority of flow.
Negate Bidirectional
Negate Bidirectional
Negate/Bi-directional
Appropriate when both forward and
reverse flow are expected, and reverse
flow will dominate, but the amount of
forward flow will be significant.
Effect of Flow Direction on mA outputs
Flow Direction
 affects how the transmitter reports flow values via the mA outputs. The mA
outputs are affected by Flow Direction only if mA Output Process Variable is set to a flow
variable.
Flow Direction and mA outputs
The effect of Flow Direction on the mA outputs depend on Lower Range Value configured for
the mA output:
If Lower Range Value is set to 0, see 
Configure process measurement
38
Micro Motion
®
 9739 MVD Transmitters